Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T07BU01256
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/05/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PLEASE PROVIDE THE VALUATION FOR THIS PROJECT PER SECTION 106.1.1 OF THE 2003 IBC. 2) PLEASE RATE THE EGRESS STAIRWAYS IN ACCORDANCE WITH THE TYPE OF CONSTRUCTION DENOTED ON THE COVER SHEET PER SECTION 106.1.1 OF THE 2003 IBC (TYPE V-A). 3) PLEASE PROVIDE ADDITIONAL STAIR, LANDING, HANDRAIL AND GUARD DETAILS IN ORDER TO VERIFY COMPLIANCE WITH CHAPTER 10 OF THE 2003 IBC. 4) PLEASE PROVIDE A SPECIAL INSPECTION FOR THE STRUCTURAL WELDING PER CHAPTER 17 OF THE 2003 IBC. 5) PLEASE REVISE DETAILS 201 AND 202 IN COORDINATION WITH THE PROVIDED STRUCTURAL CALCULATIONS PER SECTION 106.1.1 OF THE 2003 IBC. |
| 06/12/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 06/12/2007 | GBONILL1 | ENGINEERING | REVIEW | Needs Review | |
| 06/12/2007 | GBONILL1 | FIRE | REVIEW | Needs Review | |
| 06/12/2007 | GBONILL1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/12/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |