Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07BU01256
Parcel: 11703038B

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07BU01256
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) PLEASE PROVIDE THE VALUATION FOR THIS PROJECT PER SECTION 106.1.1 OF THE 2003 IBC.

2) PLEASE RATE THE EGRESS STAIRWAYS IN ACCORDANCE WITH THE TYPE OF CONSTRUCTION DENOTED ON THE COVER SHEET PER SECTION 106.1.1 OF THE 2003 IBC (TYPE V-A).

3) PLEASE PROVIDE ADDITIONAL STAIR, LANDING, HANDRAIL AND GUARD DETAILS IN ORDER TO VERIFY COMPLIANCE WITH CHAPTER 10 OF THE 2003 IBC.

4) PLEASE PROVIDE A SPECIAL INSPECTION FOR THE STRUCTURAL WELDING PER CHAPTER 17 OF THE 2003 IBC.

5) PLEASE REVISE DETAILS 201 AND 202 IN COORDINATION WITH THE PROVIDED STRUCTURAL CALCULATIONS PER SECTION 106.1.1 OF THE 2003 IBC.
06/12/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/12/2007 GBONILL1 ENGINEERING REVIEW Needs Review
06/12/2007 GBONILL1 FIRE REVIEW Needs Review
06/12/2007 GBONILL1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/12/2007 GERARDO BONILLA OUT TO CUSTOMER Completed