Permit Number: T07BU01102
Parcel: 107020120

Review Status: Completed

Review Details: RESUBMITTAL - GRADING

Permit Number - T07BU01102
Review Name: RESUBMITTAL - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: January 18, 2007
ACTIVITY NUMBER: T07BU01102
PROJECT NAME: Knittel Commercial Warehouse
PROJECT ADDRESS: 3178 North Freeway Industrial Loop
PROJECT REVIEWER: Bianca Ramirez, Engineering Associate

The following items must be revised or added to the grading plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: GRADING PLAN

1. A copy of the stamped approved Site Plan must be included with the Grading Plan submittal.

2. The Site Plan is currently in review. Any changes made to the Site Plan must be reflected on the Grading Plan. The Site Plan and Grading Plan must match.

3. The grading plan now shows off site work on the southeast side of the property. Be advised written permission form the owner and a temporary construction easement will be required for the off site work. Provide appropriate documentation with the next submittal and include the recordation data on the grading plan. Add new 10' temporary construction easement shown on last submitted site plan on the grading plan.

This comment will continue to be made until resolved; see site plan comment dated 8.27.07.

4. (Complied)

5. Provide in a general note the area of disturbance. (Complied)

This comment is from the previous review and depending on the result of the site plan comment and the above comment # 3 the area of disturbance may increase. If the temporary construction easement has work related to this project the area must be included in the area of disturbance. Revise appropriately. Be advised over an acre of disturbance a SWPPP is required. Add note indicating that area of disturbance provided includes area for temporary construction easement.

6. (Complied)

7. (Complied)

8. (Complied)

9. Clearly indicate in detail P and Q the Water Surface Elevation, Velocity and Discharge. In addition, provide soils report for recommended of setback from building for drainage channel. In addition, provide minimum 2' setback from the property line to the beginning of slope of drainage channel. Label 2' setback as 2' undisturbed area or provide appropriate documentation from property owner for encroachment within 2' area.
02/01/2008 MICHAEL ST. PAUL ZONING REVIEW Denied February 1, 2008

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

T07BU01102 Grading Plans for T07CM00480
3178 North Freeway Industrial Loop

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and until all zoning comments or concerns have been addressed.

2. We cannot verify that the grading plan is in compliance with a site plan for this site. Please submit two copies of the last approved and stamped Site Plan, Landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved development plan. Additional comments may be forthcoming.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/22/2008 CPIERCE1 OUT TO CUSTOMER Completed