Permit Number: T07BU01082
Parcel: 10321029Y

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T07BU01082
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2007 ANDREW CONNOR NPPO REVIEW Denied Submit a copy of the approved site and landscape plans for reference. The grading application will be reviewed for compliance only when the approved documents are included in the submittal. Revise grading plans as necessary to comply with the approved site plan.
08/13/2007 DAVID RIVERA ZONING REVIEW Denied 07/02/07
Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. Zoning has done a cursory review of the grading plan but cannot approve the plan at this time. The site plan must be cpompletely approved and stamped prior to approval of the grading plan.

2. Zoning could not verify that the grading plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

4. To assure approval of the grading plan please make sure that teh grading plan matches the approved site plan.
08/30/2007 JASON GREEN ENGINEERING REVIEW Denied DATE: August 30, 2007
SUBJECT: New Parking Structure for Mosaic Café Grading Plan Submittal- 2nd Engineering Review
TO: Maria Rojas
LOCATION: 2625 N Silverbell Rd, T13S R13E Sec33 Ward 1
REVIEWERS: Jason Green, CFM
ACTIVITY: T07BU01082


SUMMARY: Engineering Division of Development Services Department has received and reviewed the grading plan and geotechnical report (Pattison-Evanoff Engineering, LLC, 08MAR06). The grading plan is not approved at this time. Please address the following comments:


GRADING PLAN COMMENTS: Be advised that grading plan can not be approved prior to Site Plan approval.

DS Sec.2-02.2.1.A.14: Per site plan comment # 1: Provide the approved variance for the required maneuvering area for the loading zone that is shown on the revised site plan. Variance must be approved prior to site plan approval which must be approved prior to grading plan approval.


GENERAL COMMENTS:

Please provide an approved site plan with the approved variance for the loading zone, and a grading plan that matches the approved site plan.

For any questions or to schedule a meeting, call me at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
08/31/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
08/31/2007 SUE REEVES REJECT SHELF Completed