Permit Number: T07BU00958
Parcel: 12410005F

Address:
401 S EUCLID AV

Review Status: Completed

Review Details: REVISION - GRADING

Permit Number - T07BU00958
Review Name: REVISION - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Central City Business Park
T07BU00958
Grading Plan (1st Review)

TRANSMITTAL DATE: July 18, 2008

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. The proposed grading plan does not match the last approved grading plan or site plan, i.e. parking layout, sidewalks, building size etc. Review last approved site plan and revise grading plan to match.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t07bu00958

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plans and additional requested documents
07/24/2008 JASON GREEN ENGINEERING REVIEW Denied DATE: July 24, 2008
SUBJECT: Central City Business Park Revised Grading Plan- Engineering Review
TO: Metro Permits Express Attn: Lisa Bowers
LOCATION: 401 S Euclid, T14S R14E Sec18 Ward 5
REVIEWERS: Jason Green, CFM
ACTIVITY: T07BU00958 (Revised Grading Plan)


SUMMARY: Engineering Division of Development Services Department has received the revised grading plan (T07BU00958) for the above referenced property. Engineering Division does not recommend approval of the grading plan application at this time. The following items need to be addressed:


GRADING PLAN COMMENTS:

1) Provide a copy of the last approved site plan (T06CM06319). The grading plan can not be approved until verification that all details, locations, dimensions, and plan profiles match the approved site plan. Provide a copy of the stamped approved site plan within the grading plan package. All items on the grading plan must match the site plan plus provide additional construction information on the grading plan sheets for construction purposes. Review last approved site plan and revise grading plan to match, provide revision clouds or a detailed letter that clearly states the areas of revision.

2) Title 4 Chapter 30 R4-30-304.E.4: Revise the grading plan to provide the expiration date along with the seal for the engineer of record. Per the referenced section; "All original documents should include a notation beneath the seal either written, typed, or electronically generated that provides the day, month, and year of expiration of current registration, as shown in Appendix B. (Effective 3/08/08)."

3) Provide all supplemental information that is associated with this project at the next grading plan submittal for review. Provide a copy of the last approved site plan, Drainage Report, Geotechnical Report and revised SWPPP for a complete review of this project. No supplemental information was submitted with the review.

4) Refer to comments from Ron Brown, RA Structural Plans Examiner for all handicap and ANSI Standard requirements that apply to this project.

5) Provide a general note on the grading plan to state the following: "Call for a Pre-construction meeting prior to start of earthwork. To schedule a DSD Pre-construction meeting, SWPPP inspection or general Engineering Inspections, call IVR (740-6970), or schedule with a Customer Service Representative at the Development Services Department, or contact DSD Engineering at 791-5550 extension 2101, or schedule inspections online at: http://www.ci.tucson.az.us/dsd/Online_Services/Online_Permits/online_permits.html

6) Approval from TDOT Permits and Codes for all improvements within the public right-of-way will be required. A right-of-way use permit application will be required prior to construction, if applicable. Contact Thad Harvison, (520)-837-6592 or Thad.Harvison@tucsonaz.gov for all right-of-way requirements and permit applications.

7) Please ensure that the proposed grading plan is consistent with the site plan and Drainage Report. Grading standards may be accessed at: http://www.ci.tucson.az.us/dsd/DevStandsTOC.pdf


GENERAL COMMENTS:

Please provide the last approved site plan, 2 copies of the revised grading plan, the Drainage Report, Geotechnical Report and revised SWPPP that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments. Enclose "redlines" with the resubmittal package.

Further comments may be generated upon resubmittal of the grading plan review.

If you have any questions or to schedule an appointment call me at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
07/28/2008 ANDREW CONNOR NPPO REVIEW Denied Submit a copy of the approved site plan including landscape and native plant preservation plans for reference. The grading application will be reviewed for compliance when the approved documents are included in the submittal. Revise grading plans as necessary to comply with the approved site plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/29/2008 CINDY AGUILAR OUT TO CUSTOMER Completed
07/29/2008 CINDY AGUILAR REJECT SHELF Completed