Permit Number: T07BU00944
Parcel: 137070520

Review Status: Completed

Review Details: GRADING

Permit Number - T07BU00944
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2007 DAVID RIVERA ZONING REVIEW Approved
08/28/2007 ANDREW CONNOR NPPO REVIEW Approv-Cond
09/11/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: September 20, 2007
ACTIVITY NUMBER: T07BU00944
PROJECT NAME: Casitas at Liberty
PROJECT ADDRESS: 5031 South Liberty Avenue
PROJECT REVIEWER: Patricia Gilbert

The following items must be revised or added to the grading plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: THREE COPIES OF THE GRADING PLAN AND SWPPP.

DRAINAGE REPORT: APPROVED

1. Remove the verbiage, "20.0' PAAL," from the street cross section found on sheet 2.

2. Provide the recordation data (docket and page) for the public utility easements. Second request.

3. It appears that project may be in violation of the differential grading requirements of the development standard 11-01.8.1.A. Fills of greater than 2 feet may not be placed in the outer 100 feet of the project. Revise the proposed FFEs or provide proposed pad grades that comply with the development standard.

4. There appears to be a ponding issue at the back of lot 7 and the water surface elevation of the proposed channel. Revise the grading plan to correct the problem.

SWPPP COMMENTS

1. Provide 3 copies of the SWPPPs with the next submittal.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/21/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
09/21/2007 GERARDO BONILLA REJECT SHELF Completed