Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: September 19, 2007
ACTIVITY NUMBER: T07BU00843
PROJECT NAME: Washington Federal Savings
PROJECT ADDRESS: 4902 East Broadway Blvd.
PROJECT REVIEWER: Patricia Gilbert

The following items must be revised or added to the grading plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: GRADING PLAN, DRAINAGE REPORT


1. The proposed accessible route located at the south west corner of the property currently will not work with the traffic divider and the scupper with the linear distance provided. The current proposal shows vertical curb at the traffic divider, where an accessible ramp is required and ramp is not provided where the scupper is located. For a solution consider, providing a ramp on the north side of the traffic divider and a driveway for the ingress travel lane.
09/25/2007 DAVID RIVERA ZONING REVIEW Approved
09/27/2007 ANDREW CONNOR NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/02/2007 SHANAE POWELL OUT TO CUSTOMER Completed
10/02/2007 GERARDO BONILLA REJECT SHELF Completed