Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - GRADING ALL
Permit Number - T07BU00843
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/19/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | DATE: September 19, 2007 ACTIVITY NUMBER: T07BU00843 PROJECT NAME: Washington Federal Savings PROJECT ADDRESS: 4902 East Broadway Blvd. PROJECT REVIEWER: Patricia Gilbert The following items must be revised or added to the grading plan. Please include a response letter with the next submittal that states how all comments have been addressed. RESUBMITTAL REQUIRED: GRADING PLAN, DRAINAGE REPORT 1. The proposed accessible route located at the south west corner of the property currently will not work with the traffic divider and the scupper with the linear distance provided. The current proposal shows vertical curb at the traffic divider, where an accessible ramp is required and ramp is not provided where the scupper is located. For a solution consider, providing a ramp on the north side of the traffic divider and a driveway for the ingress travel lane. |
| 09/25/2007 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 09/27/2007 | ANDREW CONNOR | NPPO | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/02/2007 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
| 10/02/2007 | GERARDO BONILLA | REJECT SHELF | Completed |