Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07BU00616
Parcel: 133170630

Address:
350 N WILMOT RD

Review Status: Completed

Review Details: RESUBMITTAL - GRADING

Permit Number - T07BU00616
Review Name: RESUBMITTAL - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2007 HEATHER THRALL ZONING REVIEW Denied Zoning has completed the review of the grading plan.

Per DS 3-05.2.1.c.1, the minimum width of a one way PAAL shall be 12'. The grading plan shows a PAAL width at less than 12' at both one way secured entries on the west side. To reduce a PAAL width requires a Board of Adjustment variance, as PAALs are also addressed in the Land Use Code. Please revise the grading plan to ensure the PAAL width is 12' minimum.

Should you have any questions, please contact me at Heather.Thrall@tucsonaz.gov or at 837-4951. I am able to review this correction at the counter, please contact me for an appointment. Thank you.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/26/2007 VFLORES1 OUT TO CUSTOMER Completed
06/26/2007 SUE REEVES REJECT SHELF Completed