Permit Number: T07BU00615
Parcel: 13317064B

Review Status: Completed

Review Details: GRADING

Permit Number - T07BU00615
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2007 WILLDAN ENGINEERING REVIEW Approved
05/17/2007 ANDREW CONNOR NPPO REVIEW Denied 1. Submit a copy of the approved landscape and native plant preservation plans for reference. The grading application will be reviewed for compliance only when the approved documents are included in the submittal.
05/18/2007 HEATHER THRALL ZONING REVIEW Denied 1. dimension PAALs/access points (for example, C-3, PAAL south of building.) OR provide a note please that says all two way Paals are a minimum of 24' wide.

2. staff is double checking the amount of handicapped parking required for this project, per 2003 IBC. once a determination is made as to whether sufficient handicapped parking has been provided, further review on the grading plan can continue. Be advised, should further handicapped parking be required, - at least a minimum core staff review of a revised development plan is needed.

3. it appears required curbing (to protect landscaping from vehicular use area) is missing from the north part of the parking lot on page C-4 - see the islands near the far north PAAL. curbing should be all the way around islands. Check throughout the site - thickend pavement edge is not a permitted substitute for a curb requirement.

4. show curb at east end of parking lot on sheet C-5 - a curb is needed to separate the vehicle use are from unimproved property.

5. show curb at east end of parking lot at sheet C-2 as well.

6. until corrections are done and NPPO is approved, zoning cannot approve the grading plans.

7. if you have questions about this review, contact me at Heather.Thrall@tucsonaz.gov or at 837-4951.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/04/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
06/04/2007 SUE REEVES REJECT SHELF Completed