Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07BU00447
Parcel: 116300540

Review Status: Completed

Review Details: GRADING

Permit Number - T07BU00447
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2007 ANDREW CONNOR NPPO REVIEW Denied 1. Each lot within Wildcat Pass must submit a separate NPPO plan.

2. The NPPO shall include an inventory and analysis of all plants listed as Federal Endangered Species, all Saguaros, and all Ironwoods designated as Protected Native Plants according to Sec. 3.8.5. Preservation and mitigation requirements for these genus and species shall conform to Sec. 3.8.6.2.

3. To protect the natural areas, a covenant must be provided with record interest in the natural area in favor of the City of Tucson per LUC 2.8.1.7.D. Submit the required covenant or conservation easement and legal description for review

4. Include the location, size, color, and textural treatment of all retaining walls, riprapped slopes, or other constructed means of slope stabilization must be shown on one (1) of the plans submitted. Vegetation retention and re-vegetation should be used in conjunction with riprapping.

5. The grading and NPP plans shall indicate the 50-ft study area identical to the Wash Ordinance Mitigation Plan included with Case # S02-008. Include approved Wash Mitigation plan with re-submittal for reference.
04/02/2007 DAVID RIVERA ZONING REVIEW Denied 04/02/07

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved tentative plat. Please submit two copies of the approved and stamped site plan (if available), landscape, and NPPO plans with the next grading plan submittal.

a. Label and dimension the 50-foot WASH study limits.

b. The site plan can be reviewed and approved once the grading plan is approved.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved and stamped site plan. Additional comments may be forthcoming.
05/18/2007 ELIZABETH EBERBACH ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/18/2007 DELMA ROBEY APPROVAL SHELF Completed
05/18/2007 DELMA ROBEY OUT TO CUSTOMER Completed
05/18/2007 DELMA ROBEY REJECT SHELF Completed