Permit Number: T07BU00383
Parcel: 13812023C

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T07BU00383
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2007 TERRY STEVENS ZONING REVIEW Approved
09/19/2007 ANDREW CONNOR NPPO REVIEW Approved
09/28/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: June 9, 2007
ACTIVITY NUMBER: T07BU00383
PROJECT NAME: Cendot Construction
PROJECT ADDRESS: 6045 South Missiondale Road
PROJECT REVIEWER: Patricia Gilbert

The following items must be revised or added to the grading plan. Please include a response letter with the next submittal that states how all comments have been addressed.

SUBMITTAL REQUIRED: RESPONSE LETTER

RESUBMITTAL REQUIRED: GRADING PLAN

DRAINAGE REPORT IS APPROVED

1. A copy of the stamped approved Site Plan must be included with the Grading Plan submittal.

2. The Site Plan is currently in review. Any changes made to the Site Plan must be reflected on the Grading Plan. The Site Plan and Grading Plan must match.

3. Graphically indicate downspouts on sheet sd2. Provide appropriate erosion protection at the base of the down spout. Third request. DS 2-08.4.1.E.

4. In the cross section water harvesting area just west of the building, include the property line and dimension the width between the 5' sidewalk located in the ROW and the property line.

5. Provide the location of the property line and the dimension width between the property line and the sidewalk in detail sd 3. There is concern that the water harvesting area is too close to the sidewalk.

6. The scupper located on the east side of the structure is encroaching into the 5' pedestrian area. This is not approvable. The sidewalks must also be flood free for up to a ten-year event, scuppers will be required in this location. Revise the plan appropriately. Be sure the change is reflected on the site plan.

7. Provide on the grading plan the existing and proposed onsite to offsite discharge discussed in the drainage report, section 4.0. SMDDFM 12.5. This is the third request. The locations of each quantity must be shown on the plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/03/2007 DELMA ROBEY APPROVAL SHELF Completed
10/03/2007 DELMA ROBEY OUT TO CUSTOMER Completed
10/03/2007 DELMA ROBEY REJECT SHELF Completed