Permit Number: T07BU00365
Parcel: 10119001F

Review Status: Completed

Review Details: TANKS

Permit Number - T07BU00365
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07BU00365 3/13/07

1. Reconfigure permit to allow Electrical Fees.
2. Electrical Engineer shall generate plans, identify Classified location according to the requirements of NEC Article 500, and seal the plans.
3. Minimum font size is 1/8".
4. Provide power requirements for new motor loads, panel and circuit for all electrical loads, conduit and conductor size and type, disconnecting means, overcurrent protection, panel schedules, load calcs, fault calculations, and any other items as needed for a full and complete electrical design.
05/22/2007 DAVE MANN FIRE REVIEW Approved
05/22/2007 HEATHER THRALL ZONING REVIEW Approved