Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07BU00352
Parcel: Unknown

Review Status: Completed

Review Details: GRADING

Permit Number - T07BU00352
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2007 DAVID RIVERA ZONING REVIEW Denied 03/11/07

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. Zoning has reviewed the gradiong plan and finds the plan to be consistent with the CDRC approved and stamped tentative plat, the Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning will re-review the grading plan on the next submittal to ensure compliance with the CDRC approved and stamped tentative plat. Additional comments may be forthcoming.

3. Please label the subdivision boundary distance and bearings.

4. Please ensure that the grading plan matches the approved and stamped tentative plat.
03/14/2007 ANDREW CONNOR NPPO REVIEW Denied 1. All Protected Native Plants shall be planted in locations able to support their long-term health and survival per LUC 3.8.6.6.C. Demonstrate how landscape in CA/A-1 will be incorporated within details S4, N4, and O4.

2. Add note to grading plan: NPPO pre permit inspection is required prior to grading inspection can be scheduled by calling IVR system and entering inspection code 09015 or calling Landscape Field Representative directly @ 791-5550 EXT 1140.

3. Add note to grading plan: ALL LANDSCAPE AREAS SHALL BE DEPRESSED A MAXIMUM OF 6' TO ACCOMODATE WATER HARVESTING.

4. Revise grading plans as necessary to comply with the approved tentative plat.

5. The grading plan has been reviewed by the Landscape / NPPO Section but cannot approve the plan until all Engineering, comments, concerns, and appropriate revisions have been addressed.
04/11/2007 PAUL MACHADO ENGINEERING REVIEW Denied To: Rick Engineering Co. Inc. DATE: April 11, 2007
Richard Sarti
1745 E. River Road, Ste. 101
Tucson, Arizona 85741

SUBJECT: Oasis-Harrison, 1150 N. Harrison Rd.
Site plan T07BU00352 (First Review)
T14S, R15E, Section 02

RESUBMITTAL REQUIRED: Grading Plan and Drainage Report.

The Grading Plan (GP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207.
3. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10.
4. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19.
5. Show/dimension the 2' grading bench between the property line and the grading limits on details and sections.
6. Sidewalks, curbs and wheelchair ramps are required where applicable per D.S. 3-01.3.0 and installed with "Detectable Warnings" per ADAAG.
7. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21. Show curbs and sidewalk on plans even though they are shown on the paving plans. Omitting the sidewalk and curbs on the grading plan is awkward and misleading.
8. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
9. Show Grading plan number (T07BU00352) on all sheets per D.S. 2-02.2.1.29.
10. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
11. Add note: "Depress all landscaped areas 6" maximum for water harvesting".

Drainage Report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. The drainage structures may be shown on the tentative plat, however since they must have been designed by the DR, then all drainage structures shall be shown in the DR. Revise as required.
3. Prior to the release of the final grading inspection, percolation test results must be submitted to the City of Tucson, Development Services engineering division.


Stormwater pollution prevention plan:
1. The SWPPP has been accepted by engineering.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/1150 N. Harrison Rd. Grad.
.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/17/2007 DELMA ROBEY OUT TO CUSTOMER Completed
04/17/2007 SUE REEVES REJECT SHELF Completed