Permit Number: T07BU00339
Parcel: 11615085A

Review Status: Completed

Review Details: TANKS

Permit Number - T07BU00339
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide Electrical plans, prepared and sealed by an Electrical Engineer, registered in the State of Arizona. Such plans shall comply with the National Electrical Code, with special emphasis on the requirements of Chapter 5 for Classified Locations.
2. Have the Customer Service Clerk reconfigure this permit to allow the inclusion of electrical equipment.
03/16/2007 DAVE MANN FIRE REVIEW Denied Provide listings and cut sheets on new tanks and piping.

Label emergency switch on building.

Sheet FS1, bollards to be 4 feet OC maximum.

Fill out tank application form (enclosed).

Sheet G8, is piping from existing dispenser (copper) compatible with new fuel?

Final Status

Task End Date Reviewer's Name Type of Review Description
03/29/2007 FSANCHE1 OUT TO CUSTOMER Completed
03/29/2007 SUE REEVES REJECT SHELF Completed