Permit Number - T07BU00339
Review Name: TANKS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/08/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Provide Electrical plans, prepared and sealed by an Electrical Engineer, registered in the State of Arizona. Such plans shall comply with the National Electrical Code, with special emphasis on the requirements of Chapter 5 for Classified Locations. 2. Have the Customer Service Clerk reconfigure this permit to allow the inclusion of electrical equipment. |
| 03/16/2007 | DAVE MANN | FIRE | REVIEW | Denied | Provide listings and cut sheets on new tanks and piping. Label emergency switch on building. Sheet FS1, bollards to be 4 feet OC maximum. Fill out tank application form (enclosed). Sheet G8, is piping from existing dispenser (copper) compatible with new fuel? |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/29/2007 | FSANCHE1 | OUT TO CUSTOMER | Completed |
| 03/29/2007 | SUE REEVES | REJECT SHELF | Completed |