| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2007 | ANDREW CONNOR | NPPO | REVIEW | Denied | Submit a copy of the approved site plans including landscape plans for reference. The grading application will be reviewed for compliance only when the approved documents are included in the submittal. Revise grading plans as necessary to comply with the approved site plan. |
| 05/09/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | May 9, 2007 Development Services Department Zoning Review Section Michael St.Paul Planning Technician T07BU000318 Grading Plans for T06CM00000 3320 East Elvira Road Comments: 1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. In addition, we could not verify that the grading plan was in compliance with the approved development plan for Zoning Review. Please submit two copies of the approved and stamped Site Plan, Landscape, and NPPO plans with the next grading plan submittal. 3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved development plan. Additional comments may be forthcoming. 4. List the site plan activity number in the lower right corner of each sheet of the grading plan. Also list any DSMR case number with the date of approval. State the relief granted and the conditions imposed. 5. Provide the maximum slope allowed for the handicapped accessible parking (1:48 or 2% per ANSI Section 503.4). 6. All of these grading plans appear to be the same plan. 7. Please see the previous comment by David Rivera. |
| 06/15/2007 | SUNRISE ENGINEERING | ENGINEERING | REVIEW | Denied | June 11, 2007 City of Tucson 201 N. Stone Ave. Tucson, Arizona 85726 RE: Plan Review: Airport Run, Lot 113 Grading Plan Applicant: MPE Sunrise Engineering’s Civil Engineering Plan Review Team has completed the 2nd review of the following documents on behalf of the City of Tucson Development Services Department: Plans: One (1) copy (3 sheets) with cover sheet dated April 17, 2007. Drainage Report: One (1) copy dated January 30, 2007 SWPP Plan: Four (4) copies dated April 2007 These documents were reviewed only for their conformance to the City of Tucson Development Standards (Revised January 6, 2000). The following comments are remaining for the site: Grading Plan: (previous comment 6) “DS Sec. 11-01.4.1.C.2: Provide property cross section along both east and west property boundaries.” Only retention basin sections are shown. Please provide property sections or extend the retention sections in all directions to past the property lines. (previous comment 7) “Label existing contours.” Some existing contours are difficult to read. Contours along Elvira Road are not labeled. Label the road on C1.0. From Drainage Report comments. The basin cross sections do not match what is shown on the plan. The 6” pipe is shown with inverts below ground. The basin invert shown on C1.1 (20.00) does not match the plan (21.00). An additional spot elevation is required near the basin. See redlined plans. Show the two other outlet pipes on the plan. Drainage Report (typ. for all lots): On page 6, the Basin Summary shows the same Cw factor for existing and future conditions. The calculations are different in the appendices. Please refer to Table 3.4 of the City of Tucson Stormwater Detention/Retention Manual. The Cw should vary between the 2 year, 10 year, and 100 year storms as well. Please clarify. On the Drainage Maps, adding the individual flows do not equal the total Q. If you are rounding, do not show your number to 2 decimal places. Stormwater Pollution Prevention Plan: All comments are addressed. At this time we do not recommend approval. If you have any questions regarding these comments, please contact the reviewer Stephanie Schramm at 520-723-8634, between 8:00 A.M. and 5:00 P.M., Monday through Friday. Sincerely, SUNRISE ENGINEERING, Civil Engineering Plan Review Team Stephanie Schramm, P.E. Project Manager |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/26/2007 | SUE REEVES | OUT TO CUSTOMER | Completed |