Permit Number: T07BU00290
Parcel: 141090300

Address:
7970 S KOLB RD

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T07BU00290
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2007 MATT FLICK ENGINEERING REVIEW Denied Please note that the plans are confusing to review. Some items that are not shown on the Phase 1 plan appear on the Phase 2 plan (this is being submitted under 1 "BU" number and, so, is being considered as one development) and some items shown on the grading plan do not appear on the site plan.

Phase 1 Plan:

1. Provide a sidewalk along the site perimeter where none exist today. Minimum size along Anaconda Way is 5' and minimum size along Kolb Road is 6'. Please note that construction in the public right-of-way will require a right-of-way construction permit from TDOT.

2. Provide ADA-compliant ramps where sidewalks are to cross driveways or streets.

3. Provide horizontal dimensioning for the basin at the south end of the eastern parking area.

4. Please correct the overwrite located near the survey monument at the intersection of Anaconda Way and Kolb Road.

Phase 2 Plan:

A. Install 5' sidewalk along Anaconda Way where none is currently indicated.

B. Install ADA-compliant ramps where sidewalks are to cross driveways.

C. 6' is the minimum sidewalk width along Major Streets (Kolb Road) per Mayor & Council policy.

D. 2 "A" sections are shown on Sheet C1.2A.

Drainage Report:

The report is not approved. The following comments are offered:

Page 3 - The responsible party named on this page and in Appendix G do not agree.

Page 5 - The infiltration rates could not be found in Appendix G.

SWPPP:

The response from the consultant indicates a SWPPP was submitted. None appeared in the package that this reviewer had possession of. Please submit a SWPPP with the next submittal.
05/29/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: MER Corporation Expansion
T07BU00290
Grading Plan (2nd Review)

TRANSMITTAL DATE: May 29, 2007

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\grading\t07bu00290

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plans and additional requested documents
06/04/2007 ANDREW CONNOR NPPO REVIEW Denied Site plan approval is necessary to continue review.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/06/2007 DELMA ROBEY OUT TO CUSTOMER Completed
06/06/2007 SUE REEVES REJECT SHELF Completed