Permit Number: T07BU00290
Parcel: 141090300

Address:
7970 S KOLB RD

Review Status: Completed

Review Details: GRADING

Permit Number - T07BU00290
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: MER Corporation Expansion
T07BU00290
Grading Plan (1st Review)

TRANSMITTAL DATE: February 27, 2007

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 791-5608 ext. 1180.

C:\planning\grading\t07bu00290

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plans and additional requested documents
03/06/2007 ANDREW CONNOR NPPO REVIEW Denied Site plan approval is necessary to continue review.
03/14/2007 MATT FLICK ENGINEERING REVIEW Denied DSD Engineering Comments for T07CM00470/T07BU00290

1. Grade det/ret basin floor to have a minimum 0.5% slope toward the outlet end of the basin.

2. Is additional site signage contemplated? If so and if it's placed in the sight visibility triangles, the encroachments must meet the standards referenced in Dev. Std. 3-01.5.0.

3. Revise the sidewalk dimension along Anaconda Way to be 5' (minimum) per Dev. Std. 3-01.3.3. The sidewalk should extend across the entire Anaconda Way frontage.

4. Disturbance appears to be greater than 1 acre: a SWPPP is necessary unless the area of disturbance can be reduced to less than 1 acre.

Engineering is in general concurrence with Zoning and Landscape Review comments as some of these also affect issues with which Engineering is concerned. Please submit a detailed response letter addressing all comments with the next submittal.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/20/2007 FSANCHE1 OUT TO CUSTOMER Completed
03/20/2007 SUE REEVES REJECT SHELF Completed