02/28/2007 WILDAN 2ND PARTY REVIEW REVIEW Denied February 27, 2007



City of Tucson Development Services
P.O. Box 27210
Tucson, AZ 85726

RE: Giachery Avenue Swimming Pool
CITY OF TUCSON LOG NO. T07BU00185
WILLDAN PROJECT NO. 13881-7015 – 1ST REVIEW

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IRC, 2003 IBC, 2003 IMC, 2003 IECC, 1997 UAC, 2002 NEC with local modifications, and the 2003 UPC. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner John Tennant.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms


Special Inspection is required for the following items:
N/A

The following items are acceptable for deferred submittals:
N/A

GENERAL COMMENTS:
Please provide, in writing, approval for the use of the 2006 IBC by the City of Tucson Building Official.

ARCHITECTURAL COMMENTS:
Not part of this review.

STRUCTURAL COMMENTS:
Calculations indicate an active earth pressure of 30psf/ft. Please provide the soils report to justify this value or, please revise the calculations with an active pressure of 35psf/ft. Reference the City of Tucson local amendments to IBC Section 1610.1.

Please verify that there will be no surcharge on the pool’s walls due to the proximity of the CMU site/retaining walls and that there will be no surcharge on the site/retaining walls due to the proximity of the pool. Reference IBC Sections 1604.4 and 1805.3

PLUMBING COMMENTS:
Not part of this review.

MECHANICAL COMMENTS:
Not part of this review.

ELECTRICAL COMMENTS:
Not part of this review.

ENERGY CODE COMMENTS:
Not part of this review.

ACCESSIBILITY COMMENTS:
Not part of this review.

Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/tb