Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07BU00172
Parcel: 136142020

Review Status: Completed

Review Details: WALLS SUBMITTAL

Permit Number - T07BU00172
Review Name: WALLS SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2007 WILDAN BUILDING-COMMERCIAL REVIEW Denied April 17, 2007



City of Tucson Development Services
P.O. Box 27210
Tucson, AZ 85726

RE: TJ Bednar Retaining Walls
CITY OF TUCSON LOG NO. T07BU00170 through 177
WILLDAN PROJECT NO. 13881-7042 – 1ST REVIEW

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IRC, 2003 IBC, 2003 IMC, 2003 IECC, 1997 UAC, 2002 NEC with local modifications, and the 2003 UPC. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner John Tennant.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
N/A N/A N/A N/A N/A N/A

Special Inspection is required for the following items:
Masonry Construction

The following items are acceptable for deferred submittals:
N/A

GENERAL COMMENTS:
A signed special inspection form from the City of Tucson is required at the time that the plans are resubmitted for a back check. Reference the City of Tucson Submittal Policy.

ARCHITECTURAL COMMENTS:
Reviewed and accepted.

STRUCTURAL COMMENTS:
General
Please sign and seal all documents acting as construction documents in the calculation book. It is noted that the details have been stamped and signed, but the general notes sheets were not. Reference ARS Statute 32-144.

Structural Calculations
Please provide derivation of the wind load used on the free standing site wall as well as the retaining walls. 10psf is the code minimum wind, but not necessarily the design pressure. Please show that the wind load conforms to ASCE 7-02 Section 6.5.13.

PLUMBING COMMENTS:
Reviewed and accepted.

MECHANICAL COMMENTS:
Reviewed and accepted.

ELECTRICAL COMMENTS:
Reviewed and accepted.

ENERGY CODE COMMENTS:
Reviewed and accepted.

ACCESSIBILITY COMMENTS:
Reviewed and accepted.

Sincerely,

WILLDAN




Chris Kiel, C.B.O., M.C.P.
Building Official

CEK/tb

Final Status

Task End Date Reviewer's Name Type of Review Description
04/20/2007 DELMA ROBEY OUT TO CUSTOMER Completed
04/20/2007 SUE REEVES REJECT SHELF Completed