Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T07BU00008
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2007 KAROL ARAGONEZ ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Karol Aragonez
Planner

PROJECT: T07BU00008
7150 East 22nd Street
Grading

TRANSMITTAL DATE: January 4, 2007

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please call Karol Aragonez, (520) 791-5550.

S:\zoning review\planning\site review\T07BU00008.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plan, grading plan and additional requested documents
04/20/2007 MATT FLICK ENGINEERING REVIEW Denied Please note that several comments from the 1st review still apply to this submittal:

GRADING PLAN:

DSD Engineering Comments for Desert Toyota
2nd Submittal

DSD Engineering Offers The Following Comments:

1. The Project Activity Number is T07BU00008 (grading).

2. Page 6 - Portions of the storm drain within the public drainage easement shall be of material acceptable to the City Engineer. Steel or corrugated metal pipe is not an acceptable material.

3. Page 7 - Portions of the storm drain within the public drainage easement shall be of material acceptable to the City Engineer. Steel or corrugated metal pipe is not an acceptable material.

A Floodplain Use Permit application ($50 for application, + $150 for drainage report) is necessary. The grading permit will not be issued prior to approval of the floodplain permit.


Please note that the site lies within a City of Tucson flood hazard area as shown on mapping available at the DSD Engineering counter.


A Floodplain Use Permit application ($50 for application, + $150 for drainage report) is necessary. The grading permit will not be issued prior to approval of the floodplain permit.
04/27/2007 JOE LINVILLE NPPO REVIEW Denied 1) Revise the grading plan in conformance with the site/landscape plans. Review of grading plans will proceed when the site plan package is approved.

Show water harvesting areas, finished grades for screening locations and adjacent areas on the development side of the screen.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/16/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
05/16/2007 CINDY AGUILAR REJECT SHELF Completed