Permit Number: T07BU00008
Parcel: 135084520

Address:
7150 E 22ND ST

Review Status: Completed

Review Details: GRADING

Permit Number - T07BU00008
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2007 KAROL ARAGONEZ ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Karol Aragonez
Planner

PROJECT: T07BU00008
7150 East 22nd Street
Grading

TRANSMITTAL DATE: January 4, 2007

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please call Karol Aragonez, (520) 791-5550.

S:\zoning review\planning\site review\T07BU00008.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plan, grading plan and additional requested documents
01/04/2007 MATT FLICK ENGINEERING REVIEW Denied DSD Engineering Comments for Desert Toyota
1st Submittal

DSD Engineering Offers The Following Comments:

1. Place the cut and fill quantities in the General Notes.

2. The Project Activity Numbers are T07BU00008 (grading) and T07CM00016 (site).

3. Place the site address in the address block

4. Page 6 - Fill in the data for the storm drain cleanouts.

5. Page 6 - Roof drains should not discharge onto the pedestrian circulation area.

6. Page 6 - Portions of the storm drain within the public drainage easement shall be of material acceptable to the City Engineer. Steel or corrugated metal pipe is not an acceptable material.

7. Page 7 - Portions of the storm drain within the public drainage easement shall be of material acceptable to the City Engineer. Steel or corrugated metal pipe is not an acceptable material.

8. Page 12 - Please check the values for Concentration Point OS1 (see drainage report comments).

9. Sheet 13 - Please fill in the data where "XX" is shown.

10. A SWPPP is necessary for disturbance of more than 1 acre.

A Floodplain Use Permit application ($50 for application, + $150 for drainage report) is necessary. The grading permit will not be issued prior to approval of the floodplain permit.
01/16/2007 JOE LINVILLE NPPO REVIEW Denied 1) Revise the grading plan to include water harvesting areas for the street landscape borders. Grading, hydrology, and landscape structural plans are to be integrated to make maximum use of site storm water runoff for supplemental on-site irrigation purposes. LUC 3.7.4.3.B

Revise the drainage design to allow for retention of stormwater in landscape basins.

2) Submit the approved site plans including landscape plans. Review of the grading plan will be based upon the approved plans and other applicable City regulations.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/29/2007 DELMA ROBEY APPROVAL SHELF Completed
01/29/2007 DELMA ROBEY OUT TO CUSTOMER Completed
01/29/2007 GERARDO BONILLA REJECT SHELF Completed