Permit Number: T06SA00209
Parcel: 141180080

Review Status: Completed

Review Details: LUCAPPS - OVERLAY ZONE REV

Permit Number - T06SA00209
Review Name: LUCAPPS - OVERLAY ZONE REV
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2006 PAUL MACHADO ENGINEERING REVIEW Approved
08/21/2006 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Per LUC 2.8.2.6.C, "Drainageways are to be maintained in their natural states where possible...". Revise the plans to maintain the drainageway in a natural state, where possible.

The section also continues to state that "the discretionary authority shall be exercised only under unusual circumstances. In situations where the discretionary authority is exercised by the City Engineer or designee, modifications will be in accordance with the "Floodplain and Erosion Hazard Area Regulations."
08/28/2006 HEATHER THRALL ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Heather Thrall
Senior Planner

PROJECT: T06SA00209
Houghton Town Center
Scenic Corridor Overlay Zone application

TRANSMITTAL DATE: August 23, 2006

DUE DATE: August 29, 2006

COMMENTS:

1. This project is within the Scenic Corridor Overlay Zone (SCZ). Staff has reviewed this project for compliance with requirements of the SCZ, specifically outlined in LUC Section 2.8.2.

The SCZ submittal sheets will be incorporated into the Development Plan for this project. Note that the Scenic Corridor Overlay Zone submittal shall be incorporated as part of the development plan and that the sheets for that submittal shall be numbered as part of the development plan.

2. With regards to the SCZ application sheet SCZ-1, please ensure the following notations are done:

Change the building noted as 15 to read building 9 per the development plan.

3. Please add the following notations to the SCZ sheet.

Include in 30 foot buffer label the notation "30 foot undisturbed natural buffer to be preserved and maintained in it's natural state".

Please ensure the appropriate following general notes are within the 1st page of the tentative plat.

Individual SCZ case not required for each lot, but site plans, elevations, and colors must be submitted for each lot for review of compliance to Scenic Corridor Zone case number T06SA00209 for height, colors, and setbacks.

This development is subject to the review and approval of the special application for the Scenic Corridor Overlay. The Special application case number is T06SA00209 .The special application has been reviewed and approved, approval date ____, without conditions.

Maximum height of structures will be 1/3 the distance of the structure from the future right-of-way of Houghton, not to exceed 30 feet for commercial development from design grade.

No grading beyond that is necessary for siting of buildings, drives, private yards, and structural improvements. All viable vegetation with a caliper of 4 inches or greater and all saguaro cacti will be preserved or relocated on the site per the Native Plant and Preservation Ordinance.

All new utilities for development on private property or public right-of-way along Houghton Road will be underground. Trenching is permitted for the placement of utilities lines, if area is revegetated in accordance with Land Use Code Sec. 3.7.5.2.D

Building or structure surfaces, which are visible from Houghton Road will have colors, which are, predominate within the surrounding landscape.

Fencing and freestanding walls Houghton Road will meet material restrictions in Land Use Code Sec. 3.7.3, Screening Requirements.

All areas between the MS & R right-of-way line and the existing street right-of-way that are disturbed by development shall be revegetated with native vegetation.

All disturbed areas on the site that are visible from Houghton Road and are not covered by permanent improvements shall be revegetated with native plants, plants from the Drought Tolerant Plant List, or a combination of both.

Exposed cut and fill slopes shall be no greater than 1-foot rise or fall over a 3-foot length.

4. Should you have any questions, please contact me at Heather.Thrall@tucsonaz.gov or at 520-791-4541x1156.


If you have any questions about this transmittal, please call (520) 791-5608.


C:\planning\cdrc\overlay\T06SA00209 houghton town center scz.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised tentative plat.
09/08/2006 PATRICIA GEHLEN ZONING-DECISION LETTER WRITE DECISION LETTER Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

September 8, 2006

Thomas Sayler-Brown, AIA
Sayler-Brown Bolduc Lara Architects, LLC
1001 North Alvernon Way, Suite 105
Tucson, Arizona 85711

Subject: T06SA00209 Scenic Corridor Overlay Zone 8880 East Old Vail Road (D06-0013)

Dear Thomas:

Your submittal of August 16, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter for each agency explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

3 Copies Revised Overlay zone submittal package as detailed in the on line comments (Zoning, Landscape, DSD).








Should you have any questions, please call me at 791-5608, ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/


Via fax: 620-0535