Permit Number: T06PL02156
Parcel: 120086950

Address:
4832 S 12TH AV

Review Status: Completed

Review Details: PLUMBING

Permit Number - T06PL02156
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2007 DROBEY1 WWM REVIEW Needs Review
11/22/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide gas piping drawing, including the loads, developed lengths, and automatic shutoff valves.
2. Provide a vent for the hand sink and the directly-connected compartments of the 3-compartment sink.
3. Clarify the 2" trap located downstream from the 3-compartment sink. The directly-connected compartments require a trap and a vent.
4. Locate the grease trap or provide either a grease trap or a grease interceptor.
5. Provide a roof plan showing that the vents are located 10 feet away from any air intakes.