Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06PL01130
Parcel: 11615088L

Review Status: Completed

Review Details: PLUMBING

Permit Number - T06PL01130
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the location of the air gap fittings so that their flood rims are no lower than the flood rims of their associated sinks.
07/11/2006 GBONILL1 WWM REVIEW Needs Review