Permit Review Detail
Review Status: Completed
Review Details: PLUMBING
Permit Number - T06PL00832
Review Name: PLUMBING
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/18/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide cleanouts in the building sewer at intervals not exceeding 100 feet. Reference Section 719.1, UPC 2003. 2. The 2-way cleanout shown in Detail 2/C8 is in violation of Section 707.6, UPC 2003. |
06/20/2006 | AKLAPPE1 | WWM | REVIEW | Needs Review |