Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06PL00785
Parcel: Unknown

Review Status: Completed

Review Details: PLUMBING

Permit Number - T06PL00785
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/14/2006 AKLAPPE1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/14/2006 AMERY KLAPPERT OUT TO CUSTOMER Completed