Review Status: Completed
Review Details: PLUMBING
Permit Number - T06PL00452
Review Name: PLUMBING
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/16/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide specifications (i.e. listing information) for the new grease interceptor. Provide sufficient information to show that the interceptor complies with Sections H 103 and H 105, UPC 2003. 2. Provide an additional cleanout for the building drain prior to the new grease interceptor. Reference Section 707.5, UPC 2003. 3. The new grease interceptor may not accept the waste from toilets, urinals, and similar fixtures. Reference section H 102, UPC 2003. 4. Clarify the design of the natural gas piping, Differentiate between the new piping and the existing piping. Provide the developed pipe lengths between the gas meter and each gas outlet. reference Sections 103.2.3 and 1217, UPC 2003. 5. Provide information to justify the lack of an approved hood for the new convection oven. Reference Section 103.2.3, UPC 2003. |
03/17/2006 | GERRY KOZIOL | WWM | REVIEW | Approved |