Permit Number: T06PL00040
Parcel: 11706245C

Address:
211 S 5TH AV

Review Status: Completed

Review Details: PLUMBING

Permit Number - T06PL00040
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. All plans require a minimum of 1/8" type, all uppercase. Reference Section 103.2.3, UPC 2003.
2. Provide cleanouts for all sinks having horizontal waste piping. Reference Section 707.4, UPC 2003, as amended by the City of Tucson.
3. Clarify how the tubs on the 2nd floor drain to stack #9.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/23/2006 SUE REEVES REJECT SHELF Completed