Plan Number: T06PI00063
Parcel: Unknown

Review Status: Completed

Review Details: PIA SUBMITTAL

Plan Number - T06PI00063
Review Name: PIA SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2007 Blanca Espino DOT ENGINEERING REVIEW Denied 1. Approved Development Plan required for review.

2. Submit copy of the approved Geotechnical Report that recommends Pavement Section Design.
02/27/2007 ASHOFFS1 PIA COORDINATOR CUSTOMER CALLED Completed
02/27/2007 ASHOFFS1 PIA COORDINATOR OUT TO CUSTOMER Completed
12/14/2006 ASHOFFS1 ENGINEERING REVIEW Passed
12/14/2006 ASHOFFS1 UTILITY CLEARANCES COT STREETS DIVISION Denied Submit Utility Clearance Letters
12/14/2006 ASHOFFS1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied Submit Utility Clearance Letters
12/14/2006 ASHOFFS1 UTILITY CLEARANCES PC WASTEWATER MGMT Denied Submit Utility Clearance Letters
12/14/2006 ASHOFFS1 UTILITY CLEARANCES QUEST COMMUNICATION Denied Submit Utility Clearance Letters
12/14/2006 ASHOFFS1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied Submit Utility Clearance Letters
12/14/2006 ASHOFFS1 UTILITY CLEARANCES COX COMMUNICATION Denied Submit Utility Clearance Letters
12/14/2006 ASHOFFS1 UTILITY CLEARANCES SOUTHWEST GAS CORP Denied Submit Utility Clearance Letters
12/14/2006 ASHOFFS1 UTILITY CLEARANCES EL PASO NATURAL GAS Denied Submit Utility Clearance Letters
12/14/2006 ASHOFFS1 UTILITY CLEARANCES KINDER MORGAN ENERGY Denied Submit Utility Clearance Letters
12/15/2006 GARY WITTWER DOT LANDSCAPE REVIEW Approv-Cond Only drought tolerant plant materials are allowed within the ROW. This up grade requires the removal of grass within the newly dedicated ROW. Please note grass to be removed within ROW where new ROW is requested and provide notes on new landscaping.
12/19/2006 JOSE ORTIZ DOT TRAFFIC REVIEW Denied December 18, 2006
ACTIVITY NUMBER: T06PI00063
PROJECT NAME: The Pavillions
PROJECT ADDRESS: 5151 E Broadway Blvd
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan; therefore a revised PIA Plan is required for re-submittal.

The following items must be revised or added to the plan.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. The symbol used for new street signs is not used in accordance with Standard Details for Public Improvements, SD100, 2003 edition. Please add to legend.

3. Place the PIA and CDRC Case number on the cover sheet.

4. Provide a 'RIGHT LANE' (R3-5F) supplemental plaque under the new (R3-5R) along Broadway Blvd.

5. Sheet 3: Callout 25' radius returns at driveway entrance.

6. The proposed right turn lane should be designed per the PCDOT & TDOT Pavement Marking Design Manual section 4-7 and the PCDOT & TDOT Signing Manual (2002) Chap 9-5D.

7. See redlines on the submitted drawings (sheet 1-3) and address the additional redline comments. During the next submittal please re-submit the roll of redlines for back checking purposes.

8. Add the following Pavement Marking/Striping General Notes to the Plans:

'ALL STREET STRIPING & SIGNAGE TO BE COORDINATED WITH C.O.T. TRAFFIC ENGINEERING CALL 791-4259 A MINIMUM OF 48 HOURS PRIOR TO THE INSTALLATION OR REMOVAL OF ANY SIGNAGE OR STRIPING. ALL REQUIRED STRIPING AND SIGNAGE WILL BE INSTALLED AT THE CONTRACTOR'S EXPENSE. NEW STRIPING TO BE THERMOPLASTIC MATERIAL. USE 2" SQUARE-TUBE POST AND SQUARE TUBE POST FOUNDATIONS FOR SIGNING. BARRICADE PLAN MUST BE SUBMITTED TO THE CITY OF TUCSON TRAFFIC ENGINEERING FOR APPROVAL 48 HOURS IN ADVANCE OF ANY WORK IN PUBLIC RIGHT OF WAY.'

'THE CITY SHALL NOT BE LIABLE FOR ANY ERRORS AND/OR OMISSIONS ON THESE PLANS. ITEMS NOT MEETING CITY STANDARDS SHALL BE REPAIRED/REPLACED BY THE DEVELOPER/CONTRACTOR AND AT NO COST TO THE CITY.'


If you have any questions, I can be reached at 791-4259 x305 or Jose.Ortiz@tucsonaz.gov
12/27/2006 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied We have reviewed this plan and have the following comments:

1. Plans shows 4 foot wide sidewalk. Typically, we require 5 foot sidewalks on arterials.
2. Will any existing landscaping need to be relocated with this project?
3. Will there be any new landscaping with this project?
4. All work in the City right of way needs to be coordinated with Paul Rosenboom at 791-3154, ext 234 to prevent damage to existing landscaping and irrigation.

No further comments. 12/27/06