Plan Number: T06PI00049
Parcel: Unknown

Address:
2252 E BENSON HY

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T06PI00049
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2007 ASHOFFS1 UTILITY CLEARANCES COT STREETS DIVISION Completed
06/28/2007 ASHOFFS1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
06/28/2007 ASHOFFS1 UTILITY CLEARANCES PC WASTEWATER MGMT Completed
06/28/2007 ASHOFFS1 UTILITY CLEARANCES QUEST COMMUNICATION Completed
06/28/2007 ASHOFFS1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed
06/28/2007 ASHOFFS1 UTILITY CLEARANCES COX COMMUNICATION Completed
06/28/2007 ASHOFFS1 UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
06/28/2007 ASHOFFS1 UTILITY CLEARANCES EL PASO NATURAL GAS Completed
06/28/2007 ASHOFFS1 UTILITY CLEARANCES KINDER MORGAN ENERGY Completed
07/11/2007 GARY WITTWER DOT LANDSCAPE REVIEW Denied 1. NPPO approved.
2. Have you redesigned the irrigation system? Will that come under new submittal?
3. The section on Benson Highway appears to be dirt on concrete as stated in your response.
07/25/2007 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approv-Cond We have reviewed this plan and have the following comments:

1. No private irrigation lines under public roadways.
2. We understand that there will not be any landscaping installed that will be maintained by the City of Tucson.

No further comments.
07/26/2007 JOSE ORTIZ DOT TRAFFIC REVIEW Approved
07/26/2007 RICHARD LEIGH DOT ENGINEERING REVIEW Denied July 25, 2007

SUBJECT: Irvington Place, PIA Plan T06PI0049

PROJECT REVIEWER: Richard Leigh, Permits and Codes Section

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and does not recommend approval of the PIA Plan at this time. The following comments need to be addressed in the next submittal.

1. Sheet 2, Curb Access Detail: Revise as noted on red lined plan set.

2. An easement will have to be provided for the proposed retaining wall footers along Julian Crossing Way. Maintenance access should also be included in the easement.

3. Sheet 3: Provide complete right and left roadway profiles for Julian Crossing Way. Include all pertinent information. Additionally, label roadway cross slope transitions.

4. Provide a hydraulic analysis supporting the proposed storm drain across Julian Crossing Way at Sta. +/- 20+40 and the storm drain and catch basin between Sta. +/- 18+70 and 19+00, RT (Julian Crossing Way). These storm drains have not been addressed in the submitted drainage report.

5. Sheet 7: Provide a double pipe RCBC penetration detail, include dimensions.

6. Sheet 7, Detail D: Provide footer for the proposed cut-off wall. Additionally, the cut-off wall must extend to the calculated design scour depth.

7. Provide a retaining wall penetration detail for the pipe culvert crossing at 22+83 (Julian Crossing Way). Additionally, scour protection will be required for the culvert outlet.

8. Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 791-3115 ext.448 or Richard.Leigh@tucsoz.gov
09/12/2007 LHENDRI1 PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
09/12/2007 LHENDRI1 PIA COORDINATOR OUT TO CUSTOMER Completed