Plan Number: T06PI00042
Parcel: Unknown

Address:
1979 E AJO WY

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T06PI00042
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2006 TAMI HAUSER ENGINEERING REVIEW Needs Review
10/28/2006 TAMI HAUSER UTILITY CLEARANCES COT STREETS DIVISION Denied SUBMIT UTILITY CLEARANCE LETTERS.
10/28/2006 TAMI HAUSER UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied SUBMIT UTILITY CLEARANCE LETTERS.
10/28/2006 TAMI HAUSER UTILITY CLEARANCES PC WASTEWATER MGMT Denied SUBMIT UTILITY CLEARANCE LETTERS.
10/28/2006 TAMI HAUSER UTILITY CLEARANCES QUEST COMMUNICATION Denied SUBMIT UTILITY CLEARANCE LETTERS.
10/28/2006 TAMI HAUSER UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied SUBMIT UTILITY CLEARANCE LETTERS.
10/28/2006 TAMI HAUSER UTILITY CLEARANCES COX COMMUNICATION Denied SUBMIT UTILITY CLEARANCE LETTERS.
10/28/2006 TAMI HAUSER UTILITY CLEARANCES SOUTHWEST GAS CORP Denied SUBMIT UTILITY CLEARANCE LETTERS.
10/28/2006 TAMI HAUSER UTILITY CLEARANCES EL PASO NATURAL GAS Denied SUBMIT UTILITY CLEARANCE LETTERS.
10/28/2006 TAMI HAUSER UTILITY CLEARANCES KINDER MORGAN ENERGY Denied SUBMIT UTILITY CLEARANCE LETTERS.
11/03/2006 GARY WITTWER DOT LANDSCAPE REVIEW Denied 1. See #1 submittal review. Nothing submitted this round.
11/14/2006 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied We have reviewed these plans and have the following comments:

Landscaping

1. Any landscaping that is part of this project needs to be reviewed by Paul Rosenboom, 4004 S. Park Avenue, Bld #2, 791-3154 ext 234.
2. All work around existing City irrigation lines and landscaping needs to be coordinated with Paul Rosenboom at 791-3154 ext 234.

No further comments. 11/14/06
11/16/2006 JOSE ORTIZ DOT TRAFFIC REVIEW Denied November 15, 2006
ACTIVITY NUMBER: T06PI00042
PROJECT NAME: Southgate Business Park
PROJECT ADDRESS: 1979 E Ajo Way
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan; therefore a revised PIA Plan is required for re-submittal. The plans did not appear to address the previous comments posted by Traffic Engineering. Please revisit and address the comments posted below.

The following items must be revised or added to the plan.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. Sheet 5 of 6: Install an R6-1(R) "ONE WAY" Sign in the median along at both driveway locations along Ajo Way per PCDOT & TDOT Signing Manual (2002) Chap 9-3A.

3. Sheet 5 of 6: Install an R1-1 (Stop Sign) at the proposed driveway of this development off of Ajo Way (approximately Sta. 12+90) per PCDOT & TDOT Signing Manual (2002) Chap 5-11, 5-12, and Chap 9-2.

4. Sheet 5 of 6: Provide a 'RIGHTONLY' (R3-5R) under the proposed (R1-1) at the two driveways along Ajo Way

5. Sheet 5 of 6: Provide a 'RIGHT LANE' (R3-5F) supplemental plaque under all new (R3-5R) along all proposed right turn bays.

6. Sheet 5 of 6: In addition to the solid 6" white striping (WS6), for all right turn bays, raised pavement markings should be included (WS6-G20) per PCDOT & TDOT Pavement Marking Design Manual Sheet 4-13.

7. Sheet 5 of 6: Due to the configuration of the entrance at the southern entrance along the connection ramp treat the bull nose with something similar to the Pavement Marking Manual sheet 5-16 and the Signing Manual 9-5A (OM1-3 per sheet 9-14).

8. Sheet 2 of 6: Revise Striping note 1 to refer to the 2003 Edition of the PC/COT Standards and Specifications (not 1994). FYI the latest edition of the Pavement Marking Manual is 2002.

9. Sheet 2 of 6: Revise the Signing Note 1 to refer to the 2003 edition of the MUTCD (not 2000)

10. Sheet 2 of 6: revise Signing Note 6 "TYPE II" should read "TYPE IV ASTM"

11. Add the following Pavement Marking/Striping General Notes to the Plans:

'ALL STREET STRIPING & SIGNAGE TO BE COORDINATED WITH C.O.T. TRAFFIC ENGINEERING CALL 791-4259 A MINIMUM OF 48 HOURS PRIOR TO THE INSTALLATION OR REMOVAL OF ANY SIGNAGE OR STRIPING. USE 2" SQUARE-TUBE POST AND SQUARE TUBE POST FOUNDATIONS FOR SIGNING. BARRICADE PLAN MUST BE SUBMITTED TO THE CITY OF TUCSON TRAFFIC ENGINEERING FOR APPROVAL 48 HOURS IN ADVANCE OF ANY WORK IN PUBLIC RIGHT OF WAY.'



If you have any questions, I can be reached at 791-4259 x305 or Jose.Ortiz@tucsonaz.gov
11/21/2006 RICHARD LEIGH DOT ENGINEERING REVIEW Denied November 20, 2006

SUBJECT: Southgate Business Park, PIA Plan T06PI0042

PROJECT REVIEWER: Richard Leigh, Senior Engineering Associate, Permits and Codes Section

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and does not recommend approval of the PIA Plan at this time. The following must need to be addressed in the next submittal.

1. Indicate book and page on cover sheet. Plat must be recorded before submittal of mylars for final review and approval (reminder).

2. Indicate Flooplain Use permit number in note No. 21.

3. Include percent of effective air voids in pavement structural section Detail B/2.

4. Provide details for the relocation of existing streetlights.

5. Check cross section references so that they correlate with proper cross section there appears to be some confusion.

6. Include all details any proposed storm drain (bleeder pipes) within the public right-of-way for this project

If you have any questions, I can be reached at 791-3115 ext.448 or Richard.Leigh@tucsoz.gov
12/08/2006 ASHOFFS1 PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
12/08/2006 ASHOFFS1 PIA COORDINATOR OUT TO CUSTOMER Completed