Plan Number: T06PI00029
Parcel: Unknown

Address:
7600 S KOLB RD

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T06PI00029
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2006 TAMI HAUSER ENGINEERING REVIEW Denied
08/01/2006 TAMI HAUSER UTILITY CLEARANCES COX COMMUNICATION Passed SUBMIT UTILITY CLEARANCE LETTERS FOR ALL UTILITIES EXCEPT COX COMMUNICATIONS AND KINDER MORGAN.
08/01/2006 TAMI HAUSER UTILITY CLEARANCES KINDER MORGAN ENERGY Passed SUBMIT UTILITY CLEARANCE LETTERS FOR ALL UTILITIES EXCEPT COX COMMUNICATIONS AND KINDER MORGAN.
08/17/2006 GARY WITTWER DOT LANDSCAPE REVIEW Denied See previous comments. Nothing submitted this time.
08/22/2006 TAMI HAUSER UTILITY CLEARANCES SOUTHWEST GAS CORP Completed SUBMIT UTILITY CLEARANCE LETTERS FOR ALL UTILITIES EXCEPT COX COMMUNICATIONS AND KINDER MORGAN.
08/22/2006 TAMI HAUSER UTILITY CLEARANCES EL PASO NATURAL GAS Completed SUBMIT UTILITY CLEARANCE LETTERS FOR ALL UTILITIES EXCEPT COX COMMUNICATIONS AND KINDER MORGAN.
08/22/2006 TAMI HAUSER UTILITY CLEARANCES COT STREETS DIVISION Completed SUBMIT UTILITY CLEARANCE LETTERS FOR ALL UTILITIES EXCEPT COX COMMUNICATIONS AND KINDER MORGAN.
08/22/2006 TAMI HAUSER UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed SUBMIT UTILITY CLEARANCE LETTERS FOR ALL UTILITIES EXCEPT COX COMMUNICATIONS AND KINDER MORGAN.
08/22/2006 TAMI HAUSER UTILITY CLEARANCES PC WASTEWATER MGMT Completed SUBMIT UTILITY CLEARANCE LETTERS FOR ALL UTILITIES EXCEPT COX COMMUNICATIONS AND KINDER MORGAN.
08/22/2006 TAMI HAUSER UTILITY CLEARANCES QUEST COMMUNICATION Completed SUBMIT UTILITY CLEARANCE LETTERS FOR ALL UTILITIES EXCEPT COX COMMUNICATIONS AND KINDER MORGAN.
08/22/2006 TAMI HAUSER UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed SUBMIT UTILITY CLEARANCE LETTERS FOR ALL UTILITIES EXCEPT COX COMMUNICATIONS AND KINDER MORGAN.
08/28/2006 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied We have reviewed these plans and have the following comments:

1. How does the common area channel tie into the Jullian Wash?

Landscaping:

1. Please submitt the proposed landscaping plan to Paul Rosenboom at 4004 S. Park Avenue, phone 791-3154.

No further comments. 8/28/06

*********Additional Review*******

Design consultant provided information on how channel will tie into the Jullian Wash.

Landscape Comments still a concern.

No further Comments. 9/14/06
08/28/2006 Estevan Tineo DOT ENGINEERING REVIEW Denied (La Estancia De Tucson, Lots 411-664, T06PI00029, I-2006-030): The following comments, at a minimum, must be addressed in the next submittal.

1. Sheet 1 of 24: Add recordation information (Book and Page).
2. Sheet 2 of 24: Provide Floodplain Use Permit number on the plan.
3. Sheet 3 of 24: Detail C, add "No Parking" to the PDA note.
4. Sheet 3 of 24: Detail D, add "No Parking", and "4'- Sidewalk".
5. Sheet 4 of 24: Detail I, Call out 6' transition (instead of 3') for scupper.
6. Sheet 4 of 24: Detail I, Call out smooth steel painted bars not rebar.
7. Sheet 4 of 24: Detail I, Include railing in front of scupper when drop (Elev. A minus Elev. B) exceeds 1'.
8. Sheet 5 of 24: Detail C, provide 6' rectangular concrete section. Also gutter depression must not be in travel way, this includes the Bike lane (this is a safety issue).
9. Sheet 5 of 24: Detail B, Provide 6' transition. Also, is proposed grate behind gutter and will this grate perform as designed?
10. Per previous comment 19, provide structural details for proposed structures. Do not submit the plans revisions unless these details are included.
11. Sheet 20 of 24: include inlet and outlet cut-off walls.
12. Sidewalk ramp longitudinal slopes into proposed scuppers must not exceed 12:1, please check SC/7-Sheet 2/24, SC/2-Sheet 13/24, SC/4-Sheet 18/24, and SC/5-Sheet 21/24.
08/28/2006 JOSE ORTIZ DOT TRAFFIC REVIEW Approved
09/01/2006 THAUSER1 CONSTRUCTION ESTIMATE REVIEW Needs Review
09/01/2006 TAMI HAUSER PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
09/01/2006 TAMI HAUSER PIA COORDINATOR OUT TO CUSTOMER Completed