Plan Number: T06PI00028
Parcel: Unknown

Address:
461 S BRYANT AV

Review Status: Completed

Review Details: PIA SUBMITTAL

Plan Number - T06PI00028
Review Name: PIA SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2006 TAMI HAUSER UTILITY CLEARANCES COT STREETS DIVISION Passed
05/19/2006 TAMI HAUSER ENGINEERING REVIEW Needs Review
05/19/2006 TAMI HAUSER UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Passed
05/19/2006 TAMI HAUSER UTILITY CLEARANCES PC WASTEWATER MGMT Passed
05/19/2006 TAMI HAUSER UTILITY CLEARANCES QUEST COMMUNICATION Passed
05/19/2006 TAMI HAUSER UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Passed
05/19/2006 TAMI HAUSER UTILITY CLEARANCES COX COMMUNICATION Passed
05/19/2006 TAMI HAUSER UTILITY CLEARANCES SOUTHWEST GAS CORP Passed
05/19/2006 TAMI HAUSER UTILITY CLEARANCES EL PASO NATURAL GAS Passed
05/19/2006 TAMI HAUSER UTILITY CLEARANCES KINDER MORGAN ENERGY Passed
06/06/2006 GARY WITTWER DOT LANDSCAPE REVIEW Approved No Comment
06/06/2006 DALE KELCH DOT TRAFFIC REVIEW Denied approval 48 hours in advance of any work in public right-of-way.”

Add the following note: “The City shall not be liable for any errors and/or omissions on these plans. Items not meeting City standards shall be repaired/replaced at no cost to the City.”

Show existing school crosswalk (Brown Way) and indicate that this crosswalk shall be reinstalled as white thermoplastic. Indicate removal of existing school ped crossing signs and advance school ped crossing signs.

Add this note: “All school warning signs shall be fluorescent yellow-green diamond-grade (DG3 or equivalent) sheeting.”

Indicate pavement markings for the bus bay. Use WS8 (white solid eight-inch) for solid stripe. Use WG8 (2x6) for the dashed line. (This nomenclature is defined in the City of Tucson/Pima County Pavement Marking Design Manual. Please use our standards to define these pavement markings.)

Add Advance Warning S-1 + W16-9p approx. 125 in advance of the new school crosswalk. Indicate that the new signs are installed on 2” square tube posts and square tube post foundations.

For the new S1-1s at the new school crosswalk, indicate that each new sign is installed on 2” square tube posts and square tube post foundations.

Indicate the curb shall be painted red from Station 4+24 to Station 5+55

Show existing (white) crosswalk at Marion Trail. Indicate as “existing.”

On the east side of the new crosswalk, the new S1-1 is shown to be installed in the middle of a handicap ramp. Please move the leader line to indicate that the sign is to be installed to the north of the ramp.




Diahn L. Swartz, P.E., PTOE
Traffic Engineering Project Manager
City of Tucson
201 N. Stone Ave, 5th Floor
PO Box 27210
Tucson AZ 85726-7210

(520) 791-4259
(520) 791-5526

Diahn.Swartz@tucsonaz.gov
06/06/2006 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approved We have reviewed these plans and have no comments. Should there be major changes to the submitted plan, we would require another review.

6/6/06
06/14/2006 TAMI HAUSER PIA COORDINATOR CUSTOMER CALLED Completed
06/14/2006 Blanca Espino DOT ENGINEERING REVIEW Denied PIA Plan
1. Please include a response letter with the next submittal that states how all comments have been addressed. Include plans/redlines from previous plan submittal.

2. Correct and revise title block heading to read; Lineweaver Elementary School Busbay Modifications on Bryant Avenue.

3. In title block, add assigned I-Plan Number, I-2006-029 to cover sheet.

4. Developer and owner should be on cover sheet.

5. Indicate an Administrative address for project.

6. Bench Mark information must refer a COT field Book and page. Correct and revise.

7. Indicate a dimensioned structural pavement detail. See redlines for location.

8. Indicate a dimensioned detail for each curb access ramp. Truncated Domes required.

9. Indicate the Radius, Stationing, Point of Curvature and/or Point of Reverse Curvature for each curb to be constructed.

10. Indicate a dimensioned scupper detail if it is to be modified.

11. Add note to General or Paving Notes: Signage and striping should be coordinated with Traffic Engineering and installed at no expense to the public. Call Traffic Engineering at 791-4259 prior to the installation or removal of striping and signage.

12. Add note to General or Paving Notes: Engineer of Record must provide written documentation that all utilities within the right of way have been cleared for construction.

13. Add note to General or Paving Notes: All changes to these plans must be approved by the City of Tucson City Engineer's Permits and Codes Unit prior to construction.

14. Add note to General or Paving Notes: The City shall not be held liable for any errors and/or omissions on these plans. Items not meeting City Standards shall be repaired/replaced at no cost to the City.

15. Add note to General or Paving Notes: The Engineer of Record shall submit to the City for acceptance any changes to the approved plans prior to construction. Additionally, the Engineer of Record shall certify all changes meeting all applicable standards, codes, and ordinances.

16. Add note to General or Paving Notes: An excavation permit shall be obtained from the City of Tucson Transportation Department prior to any work within the Public right-of-way.

17. Add note to General or Paving Notes: A pre-construction field meeting shall be conducted with the City of Tucson Transportation inspector prior to any work within the public right-of-way.

18. Add note to General or Paving Notes: The extent and type of surface treatments/repairs indicated on the plans may not be all inclusive of the work that is needed. Additional repairs, paving, or replacement may be needed depending on field conditions.
06/14/2006 TAMI HAUSER PIA COORDINATOR OUT TO CUSTOMER Completed