Plan Number: T06PI00023
Parcel: Unknown

Address:
7600 S KOLB RD

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T06PI00023
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2006 TAMI HAUSER ENGINEERING REVIEW Needs Review
08/01/2006 TAMI HAUSER UTILITY CLEARANCES COT STREETS DIVISION Completed
08/01/2006 TAMI HAUSER UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
08/17/2006 GARY WITTWER DOT LANDSCAPE REVIEW Denied Please submit a copy of you Landscape and Irrigation plan for common area A. Private irrigation lines can not be placed under public roadways.
08/17/2006 JOSE ORTIZ DOT TRAFFIC REVIEW Approved
08/22/2006 TAMI HAUSER UTILITY CLEARANCES PC WASTEWATER MGMT Completed
08/22/2006 TAMI HAUSER UTILITY CLEARANCES QUEST COMMUNICATION Completed
08/22/2006 TAMI HAUSER UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed
08/22/2006 TAMI HAUSER UTILITY CLEARANCES COX COMMUNICATION Passed
08/22/2006 TAMI HAUSER UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
08/22/2006 TAMI HAUSER UTILITY CLEARANCES EL PASO NATURAL GAS Completed
08/22/2006 TAMI HAUSER UTILITY CLEARANCES KINDER MORGAN ENERGY Passed
08/28/2006 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied We have reviewed these plans and have the following comments:

Landscaping

1. Sheet 2 of 12 - Note 23- Please correct Paul Rosenboom's extension to 234.
2. Please provide the proposed landscape plan for the landscape areas within the right of way that the City will be responcible for maintaining. This plan should be directed to Paul Rosenboon at 4004 S. Park Avenue - Phone 791-3154 ext 234.

No further comments. 8/28/06
08/30/2006 Estevan Tineo DOT ENGINEERING REVIEW Denied La Estancia De Tucson, Lots 331-410
The following comments, at a minimum, must be addressed in the submittal.

1. Sheet 2 of 12: Provide the Floodplain Use Permit number. Note, this permit should cover all floodplains, including related drainage infrastructure in the r/w.
2. Sheet 3 of 12: Detail B, Add "NO PARKING" in the PAD description.
3. Sheet 3 of 12: Detail C, Add "NO PARKING" and "4'-SIDEWALK" in the PAD description.
4. Sheet 4 of 12: Detail C, provide rectangular concrete transition.
5. Sheet 4 of 12: Detail C, no gutter depression in pavement section, this includes the bike lane. Please revise.
6. Sheet 4 of 12: Detail B, is proposed catch basin behind curb line? Will this type of design convey drainage on a continuous grade?
7. Sheet 6 of 12: The plans must refer to paving plans (I-2006-####) not plan review tracking numbers (T06PI-####), please revise accordingly.
8. General Comment: Given that this project (La Estancia) contains phases that depend on other phases, add the following note (or something similar): PIA Paving Plan I-200#-####, I-200#-####,..etc., as applicable must be installed and accepted prior to the construction of these improvements.
9. Sheet 7 of 12: Please indicate the appropriate paving plan numbers, not pia tracking numbers, for those items to be built on other plans (Typical).
10. Sheet 8 of 12: Plan indicates an existing RCP? And with less than 12" of cover? Please indicate the PIA Paving Plan number for the RCP to be built and make sure the pipe (and all other pipes) have adequate cover, the pipe crown must be below the pavement section.
11. Previous comment 20. Please note, A CLOMR must be obtained for FEMA floodplains prior to construction in FEMA floodplain. Revise plans accordingly.
09/01/2006 THAUSER1 CONSTRUCTION ESTIMATE REVIEW Needs Review
09/01/2006 TAMI HAUSER PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
09/01/2006 TAMI HAUSER PIA COORDINATOR OUT TO CUSTOMER Completed