Plan Number: T06PI00016
Parcel: Unknown

Address:
7600 S KOLB RD

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T06PI00016
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2006 TAMI HAUSER ENGINEERING REVIEW Needs Review
07/11/2006 THAUSER1 CONSTRUCTION ESTIMATE REVIEW Needs Review
07/11/2006 TAMI HAUSER UTILITY CLEARANCES QUEST COMMUNICATION Completed PLEASE SUBMIT UTILITY LETTERS FOR COX COMMUNICATIONS AND KINDER MORGAN. IF THESE ARE NOT APPLICABLE YOU NEED TO SUBMIT THE LETTERS WITH NOT APPLICABLE STATES ON THEM.
07/11/2006 TAMI HAUSER UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed PLEASE SUBMIT UTILITY LETTERS FOR COX COMMUNICATIONS AND KINDER MORGAN. IF THESE ARE NOT APPLICABLE YOU NEED TO SUBMIT THE LETTERS WITH NOT APPLICABLE STATES ON THEM.
07/11/2006 TAMI HAUSER UTILITY CLEARANCES COX COMMUNICATION Passed PLEASE SUBMIT UTILITY LETTERS FOR COX COMMUNICATIONS AND KINDER MORGAN. IF THESE ARE NOT APPLICABLE YOU NEED TO SUBMIT THE LETTERS WITH NOT APPLICABLE STATES ON THEM.
07/11/2006 TAMI HAUSER UTILITY CLEARANCES SOUTHWEST GAS CORP Completed PLEASE SUBMIT UTILITY LETTERS FOR COX COMMUNICATIONS AND KINDER MORGAN. IF THESE ARE NOT APPLICABLE YOU NEED TO SUBMIT THE LETTERS WITH NOT APPLICABLE STATES ON THEM.
07/11/2006 TAMI HAUSER UTILITY CLEARANCES EL PASO NATURAL GAS Completed PLEASE SUBMIT UTILITY LETTERS FOR COX COMMUNICATIONS AND KINDER MORGAN. IF THESE ARE NOT APPLICABLE YOU NEED TO SUBMIT THE LETTERS WITH NOT APPLICABLE STATES ON THEM.
07/11/2006 TAMI HAUSER UTILITY CLEARANCES KINDER MORGAN ENERGY Passed PLEASE SUBMIT UTILITY LETTERS FOR COX COMMUNICATIONS AND KINDER MORGAN. IF THESE ARE NOT APPLICABLE YOU NEED TO SUBMIT THE LETTERS WITH NOT APPLICABLE STATES ON THEM.
07/11/2006 TAMI HAUSER UTILITY CLEARANCES COT STREETS DIVISION Completed PLEASE SUBMIT UTILITY LETTERS FOR COX COMMUNICATIONS AND KINDER MORGAN. IF THESE ARE NOT APPLICABLE YOU NEED TO SUBMIT THE LETTERS WITH NOT APPLICABLE STATES ON THEM.
07/11/2006 TAMI HAUSER UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed PLEASE SUBMIT UTILITY LETTERS FOR COX COMMUNICATIONS AND KINDER MORGAN. IF THESE ARE NOT APPLICABLE YOU NEED TO SUBMIT THE LETTERS WITH NOT APPLICABLE STATES ON THEM.
07/28/2006 DALE KELCH DOT TRAFFIC REVIEW Approved
08/03/2006 GARY WITTWER DOT LANDSCAPE REVIEW Denied Revised NPPO and Landscape plan not received.
08/04/2006 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied We have reviewed these plans and have the following comments:

1. Sheet 3 of 26 - Detail C - This detail shows a landscape area. Who will maintain this area?
2. General - There are several sidewalk scuppers shown on the plans. It appears that there is erosion protection at each of the outlets. Please verify that there is erosion protection at the outlets.

No further comments. 8/4/06
08/09/2006 Estevan Tineo DOT ENGINEERING REVIEW Denied 8/8/2006 (T06PI000016) La Estancia De Tucson Lots 1-330

The following comments, at a minimum, must be addressed in the next submittal:

1. Darken the font for all r/w improvements, including sidewalk and ramps. The font for existing items in the r/w (for example sewer lines) should be lightened (typical comment).
2. Sheet 3 of 26: Details C and D, state which items the PAD covers. For example, for detail C, state "No-Parking" and for Detail D state "No-parking and 4'-sidewalk".
3. Sheet 4 of 26: The proposed scuppers must not result in sidewalk running slopes, on both sides of the scuppers, exceed 12:1. Please check all scuppers.
4. Sheet 5 of 26: (Previous comment 17) Details B and C are not very clear and still indicates gutter depression in the roadway travel way. Revise catch basin design accordingly.
5. Previous comment 18, call out cur transitions. For example the plan view, for all the sheets, depict curb transitions but does not call out the appropriate detail (For example each depicted curb transition would make reference to Detail 210). Revise.
6. Previous comment 19, the plans must call out which ramp detail is to be used at each ramp location. Revise.
7. Proposed ramps should line up to each other, for example Sheet 9/26 indicates two ramps, one at station 173+27.62, 13' LT and corresponding ramp at 172+92.68, 13 RT (35' apart). Please revise ramps and check all the other ramps and revise as needed.
8. Previous comment 32 and 33: Detail J/4 indicates a modified wall transition and refers to B-08.10. Detail B-08.10 indicates 4' cutoff walls. Per ADOT Standard Details provide the appropriate cutoff walls.
9. Sheet 8 of 26, profile view of scupper 18 (SC/18) seems to indicate a sidewalk slope greater than 12:1. Revise sidewalk slope and check remaining scuppers.
08/22/2006 TAMI HAUSER UTILITY CLEARANCES PC WASTEWATER MGMT Completed PLEASE SUBMIT UTILITY LETTERS FOR COX COMMUNICATIONS AND KINDER MORGAN. IF THESE ARE NOT APPLICABLE YOU NEED TO SUBMIT THE LETTERS WITH NOT APPLICABLE STATES ON THEM.
08/23/2006 TAMI HAUSER PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
08/23/2006 TAMI HAUSER PIA COORDINATOR OUT TO CUSTOMER Completed