Plan Number: T06PI00016
Parcel: Unknown

Address:
7600 S KOLB RD

Review Status: Completed

Review Details: PIA SUBMITTAL

Plan Number - T06PI00016
Review Name: PIA SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2006 GARY WITTWER DOT LANDSCAPE REVIEW Denied 1. Please provide the approved site NPPO Plan.
2. Please submit your landscape and irrigation plans for the common areas - Note: Private irrigation lines can not be placed under public roadways. If you have questions, please call me at 791-5100.
05/05/2006 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied We have reviewed these plans and have the following comments:

1. Page 4 - Detail E - Need to call out the use of truncated domes on this detail.
2. General - What is planned for the common areas? If there will be landscaping and irrigation, we will need additional information. Also, who will be responcible for the maintenance of the common areas?

No further comments. 5/5/06
05/08/2006 Estevan Tineo DOT ENGINEERING REVIEW Denied Please note first submittal of these plans.

The following comments, at a minimum, must addressed in the next submittal:
1. Sheet 1 of 25: Provide Project Title on top of cover sheet.
2. Sheet 1 of 25: Provide recordation for public r/w under project title (Book and Page).
3. Sheet 1 of 25: Provide project adminstrative address on cover sheet.
4. Sheet 1 of 25: Remove "City of Tucson Develoment Review" signatory line.
5. Sheet 2 of 25: Provide the notes as attached on Sheet 2 of 5.
6. Sheet 3 of 25: Remove detail B.
7. Sheet 3 of 25: Detail D, Provide DSMR number for proposed no parking signage.
8. Sheet 3 of 25: Detail D, provide 5' sidewalk as per Development Standards.
9. Sheet 3 of 25: Pavement Sections 1 and 2, call-out pavement mix no.
10. Sheet 4 of 25: Provide ramp for Detail K per ADA standards.
11. Sheet 4 of 25: Detail H, provide 5' landing.
12. Sheet 4 of 25: Section H-H, call out 12:1 max ramp approach.
13. Sheet 4 of 25: Section H-H, Elevation View, call out 5' landing width.
14. Sheet 4 of 25: Provide cross bars for scuppers 18 and 21.
15. Sheet 4 of 25: Detail E, call out 5' sidewalk width and 5' ramp width.
16. Sheet 5 of 25: Detail A, include sheet number for each scupper called out.
17. Sheet 5 of 25: Scupper and Catch basin details, revise detail such that gutter depression is outside of lane per Detail 306, note 10.
18.Typical comment: call out curb transition from wedge to vertical as applicable.
19. Sheet 7 of 25: Call out ramp detail reference (Typical).
20. Sheet 7 of 25: Provide handicap access ramps at about station 151+50.
21. Sheet 7 of 25: Provide handicap access ramps at about station 158+00.
22. Sheet 8 of 25: Provide handicap access ramps at about station 161+00.
23. Typcial comment, provide and call=out survey monumenation.
24. Sheet 8 of 25: Provide handicap access ramps at about station 168+00.
25. Sheet 9 of 25: Provide handicap access ramps at about station 171+00.
26. Sheet 10 of 25: Provide handicap access ramps at about station 293+00.
27. Sheet 10 of 25: Provide handicap access ramps at about station 296+00.
28. Sheet 11 of 25: Provide handicap access ramps at about station 302+00.
29. Sheet 11 of 25: Provide handicap access ramps at about station 305+00.
30. Sheet 13 of 25: Provide handicap access ramps at about station 336+00.
31. Sheet 14 of 25: Call type of box culvert (ADOT B###).
32. Sheet 14 of 25: Call out headwall/wing walls for proposed box culvert.
33. Sheet 14 of 25: Call out cutt-off walls and depth.
34. Sheet 15 of 25: Provide handicap access ramps at about station 363+00.
35. Sheet 16 of 25: Provide handicap access ramps at about station 368+00.
36. Sheet 16 of 25: Provide handicap access ramps at about station 376+00.
37. Sheet 18 of 25: Provide handicap access ramps at about station 422+33 and 425+50.
38. Sheet 23 of 25: Line-up pipe crowns from 66" to 60" RCP.
05/12/2006 TAMI HAUSER UTILITY CLEARANCES COT STREETS DIVISION Needs Review
05/12/2006 TAMI HAUSER ENGINEERING REVIEW Needs Review
05/12/2006 TAMI HAUSER UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Needs Review
05/12/2006 TAMI HAUSER UTILITY CLEARANCES PC WASTEWATER MGMT Needs Review
05/12/2006 TAMI HAUSER UTILITY CLEARANCES QUEST COMMUNICATION Needs Review
05/12/2006 TAMI HAUSER UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Needs Review
05/12/2006 TAMI HAUSER UTILITY CLEARANCES COX COMMUNICATION Needs Review
05/12/2006 TAMI HAUSER UTILITY CLEARANCES SOUTHWEST GAS CORP Needs Review
05/12/2006 TAMI HAUSER UTILITY CLEARANCES EL PASO NATURAL GAS Needs Review
05/12/2006 TAMI HAUSER UTILITY CLEARANCES KINDER MORGAN ENERGY Needs Review
05/17/2006 DALE KELCH DOT TRAFFIC REVIEW Denied Traffic Engineering REJECTS this PIA submittal:

1. Sheet 15/25, Sta 360+56, 16.5' lt has "new sign" called out without identifying the type of sign. It should be an R1-1.

2. Sheet 20/25, Sta 446+43, 13' rt and 447+55, 13' lt have signs depicted that are not called out. Both should be R1-1 signs.

3. Sheet 20/25, Sta 440+69, 16.5' rt has a no parking sign called out. This should be an R1-1 sign.

4. Sheet 22/25, Sta 464+01, 16.5' lt has a no parking sign called out. This should be an R1-1 sign.

5. Sheet 23/25 and 24/25, all R1-1 signs that appear on these sheets (stop control before crossing Via Pampas Morenas) need to be called out on these sheets, regardless of them being identified on other sheets.

6. Sheet 24/25, Sta 118+35, 25.5' rt has a no parking sign called out. This should be an R1-1 sign.

7. The section for Via Pampas Morenas is identified as detail C/3 on sheet 3, but the section bubbles on sheets 23, 24 call out section F/3.

8. Via Pampas Morenas should identify that there is no parking. Show no parking signs in detail C/3 and in plan view on sheets 23, 24.

9. Show no parking sign in detail D/3.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
05/17/2006 TAMI HAUSER PIA COORDINATOR CUSTOMER CALLED Completed
05/17/2006 TAMI HAUSER PIA COORDINATOR OUT TO CUSTOMER Completed