Plan Number: T06PI00011
Parcel: Unknown

Address:
131 W ELVIRA RD

Review Status: Completed

Review Details: PIA SUBMITTAL

Plan Number - T06PI00011
Review Name: PIA SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2006 Blanca Espino DOT ENGINEERING REVIEW Denied PIA Plan
1. Please include a response letter with the next submittal that states how all comments have been addressed. Include plans/redlines from previous plan submittal.

2. Title blocks should look like the attached copy. See attached. Correct and revise.

3. Sheet 1, add Plan Number I-2006-007 to all sheets. Correct and revise.

4. Sheet 1, indicate and label Elvira Road & Missiondale Road in location map. Correct and revise.

5. Sheet 1, General Note 3 must reference a City of Tucson field Book and Page. Correct and revise.

6. Add note to General or Paving Notes: Engineer of Record must provide written documentation that all utilities within the right of way have been cleared for construction.

7. Add note to General or Paving Notes: All changes to these plans must be approved by the Tucson City Engineer's Permits and Codes Unit, prior to construction.

8. Add note to General or Paving Notes: The contractor shall contact and/or coordinate any work with COT Streets & Traffic Maintenance Division, Median Island Maintenance Section (791-5279, ext. 234) prior to disturbing any COT/DOT landscaping or irrigation systems. Additionally, the contractor shall repair or replace any disturbed COT/DOT landscaping or irrigation systems, including replacement of any damaged plants.

9. Add note to General or Paving Notes: Floodplain Use Permit No._______, has been issued by Development Services Department for work impacting City and FEMA Floodplains.

10. If applicable, add note to General or Paving Notes: The Engineer of Record shall field verify that the "saw cut" line is located within competent pavement. Adjustments to the plan shall be documented and As-built; a one foot minimum shall be provided."

11. Sheet 1 & 2, indicate Douba Lane and Radec Lane to be Private Streets as per the approved Tentative Plat. Correct and revise.

12. Sheet 2, Indicate correct street name "Missiondale Road" in place of Midvale Road. Correct and revise.

13. Sheet 2, Indicate details how Radec Lane ties in to Elvira Road. Also indicate existing & new right of way, survey control lines, existing & new curbs, stationing, notes, all existing & new utility systems. Correct and revise.

14. Sheet 2, Indicate elevations and or stationing for curb, curb return and each type handicap ramp.

15. Sheet 2, Profile portion, use a lighter line weight for horizontal lines to signify elevations per foot. Proposed line weight too busy. Correct and revise.

16. Sheet 2, A profile is needed for pavement widening projects (Deceleration/Acceleration lanes).

17. Sheet 2, Plan and Profile portion shall show existing grades at both right of way lines and centerline alignment. New grades shall be shown at centerline and both top of curb and gutter. All control lines will show elevations, stationing, percent of grade and all necessary related profiles pertaining to existing sanitary sewers, storm sewers and utilities. Correct and revise.

18. Sheet 2, Detail portion shall show existing and proposed manholes, drainage structures, cross-sections, handicap ramps (all types that are proposed), structural details. Details will be dimensioned and identified as Standard Details.

19. Sheet 2, Detail; Section AA shall indicate existing and proposed street slope/grade (s). Correct and revise.

20. Sheet 2, Indicate Curve and Line data on plan set.

21. Refer to redlines from 1st submittal for additional corrections.
03/15/2006 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied We have reviewed these plans and have the following comments:

1. Please provide a Streets and Traffic Maintenance Signature block on sheet 1.
2. Sheet 1 - Note 8 & 17 - these notes are duplicated.
3. Sheet 2 - No station and offset information is given for the sawcutting, new curb, and new sidewalk.
4. Sheet 2 - The plan calls for a new curb acess ramp at Midvale and Duba Lane. Is the curb acess ramp on the south side of this intersection new, or existing?
5. These plans show one of the roads as Midvale and Missiondale. Which is correct?

No further comments. 3/15/06
03/16/2006 GARY WITTWER DOT LANDSCAPE REVIEW Denied 1. Please submit a copy of your approved NPPO plan. Native plants that are within the ROW should be included on this plan.
2. On the north side of you project, along Elvira, the City has an existing irrigation line that waters trees. This was a neighborhood project and must stay in place. Please add a note to you plans " The contractor shall provide a 4" PVC Sch. 40 sleeve under the driveway. Extend sleeve 12" past paving. Cut the existing irrigation line, install line in sleeve and reconnect the line. Call 791-5279 ext. 234 for inspection prior to covering pipe.
3. Please add a note " The existing trees and irrigation line and all equipment must be protected in place. Any damage to the trees or pipe must be repaired or replaced by the contractor at his expense."
03/21/2006 THAUSER1 ENGINEERING REVIEW Needs Review SUBMIT UTILITY CLEARANCE LETTERS
03/21/2006 THAUSER1 ENGINEERING UTILITY AWARENESS NOTIFICATION Denied SUBMIT UTILITY CLEARANCE LETTERS
03/27/2006 DALE KELCH DOT TRAFFIC REVIEW Approved Traffic Engineering recommends APPROVAL of this PIA submittal.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
03/28/2006 TAMI HAUSER PIA COORDINATOR CUSTOMER CALLED Completed
03/28/2006 TAMI HAUSER PIA COORDINATOR OUT TO CUSTOMER Completed