Plan Number: T06PI00008
Parcel: Unknown

Address:
1701 W EL RIO DR

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T06PI00008
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2006 Estevan Tineo DOT ENGINEERING REVIEW Denied 3/22/2006 The following items, at a minimum, must be addressed in the next submittal (Tully Elem School Bus Bay T06PI00008).
1. Plans call out 14" curb reveal but existing as-built plan (I-90-38) and field inspection noted 6" curb reveal? The proposed "bump-out" curbing must match surrounding curbing reveal and type.
2. Call out concrete slab slope in section A (minimum 1%, maximum 2%).
03/29/2006 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approved We have reviewed these plans and have the following comments:

Previous comments have been addressed. No further comments. 3/29/06
03/31/2006 TAMI HAUSER UTILITY CLEARANCES COT STREETS DIVISION Passed
03/31/2006 TAMI HAUSER ENGINEERING REVIEW Needs Review
03/31/2006 TAMI HAUSER UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Passed
03/31/2006 DALE KELCH DOT TRAFFIC REVIEW Approved Traffic Engineering recommends APPROVAL of this PIA submittal.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
03/31/2006 TAMI HAUSER UTILITY CLEARANCES PC WASTEWATER MGMT Passed
03/31/2006 THAUSER1 CONSTRUCTION ESTIMATE REVIEW Needs Review
03/31/2006 TAMI HAUSER UTILITY CLEARANCES QUEST COMMUNICATION Passed
03/31/2006 TAMI HAUSER UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Passed
03/31/2006 TAMI HAUSER UTILITY CLEARANCES COX COMMUNICATION Passed
03/31/2006 TAMI HAUSER UTILITY CLEARANCES SOUTHWEST GAS CORP Passed
03/31/2006 TAMI HAUSER UTILITY CLEARANCES EL PASO NATURAL GAS Passed
03/31/2006 TAMI HAUSER UTILITY CLEARANCES KINDER MORGAN ENERGY Passed
04/03/2006 TAMI HAUSER PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
04/03/2006 TAMI HAUSER PIA COORDINATOR OUT TO CUSTOMER Completed