Plan Number: T06PI00008
Parcel: Unknown

Address:
1701 W EL RIO DR

Review Status: Completed

Review Details: PIA SUBMITTAL

Plan Number - T06PI00008
Review Name: PIA SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2006 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approv-Cond We have reviewed these plans and have the following comments:

1. Top of Curb and Gutter elevation shown in the bus bay modification is not readable.
2. Only one gutter elevation is provided for the modifications. Please make sure that there is positive drainage and no ponding.

No further comments. 2/23/06
02/24/2006 Estevan Tineo DOT ENGINEERING REVIEW Denied The following items, at a minimum, must be addressed in the next submittal (Tully Elem School Bus Bay - T06PI00008).

1. Page 1 of 1: Please include the standard notes as checked on the sheet attached on the sheet.
2. Page 1 of 1: Remove note 18, Inspection issues are covered in the PIA contract.
3. Page 1 of 1: Title Block, move Streets and Engineering Admin signature lines up one row.
02/28/2006 THAUSER1 ENGINEERING REVIEW Needs Review
02/28/2006 THAUSER1 ENGINEERING UTILITY AWARENESS NOTIFICATION Needs Review
03/02/2006 GARY WITTWER DOT LANDSCAPE REVIEW Approved
03/06/2006 DALE KELCH DOT TRAFFIC REVIEW Denied Traffic Engineering REJECTS this PIA submittal:

1. The title of the referenced manual is "The Manual ON Uniform..." not of. Correct general note 10.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
03/13/2006 THAUSER1 PIA COORDINATOR CUSTOMER CALLED Completed
03/13/2006 THAUSER1 PIA COORDINATOR OUT TO CUSTOMER Completed