Plan Number: T06PI00002
Parcel: Unknown

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T06PI00002
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2006 THAUSER1 ENGINEERING REVIEW Needs Review
03/21/2006 Estevan Tineo DOT ENGINEERING REVIEW Denied (March 21, 2006) Permits and Codes has reviewed the proposed project (T06PI00002) and included the following comments. The next submittal must address these comments, at a minimum, and include in writing how each comment was addressed.

1. Previous comment 1 "1. Sheet 1 of 4: Provide the Book and Page under the Title" not addressed. Provide the recordation information for the new subdivision not for the existing subdivision.
2. Previous comment 2 addressed.
3. Previous comment 3 "3. Will the sewer be installed before the right-of-way Improvements? If so then prepare a separate sewer plan for Pima County Waste Water and DOT review." Not addressed. A separate plan was provided, however the sewer plan review is not part of the PIA process and must be submitted separately. The sewer plan must be submitted to DOT and Pima county directly.
4. Previous comment 4 addressed.
5. Previous comment 5 addressed.
6. Previous comment 6 addressed.
7. Previous comment 7 addressed.
8. Previous comment 8 not fully addressed. Roadway profile provided, however profile stationing should line-up with plan view stationing as typically practiced in the profession.
9. Previous comment 9 addressed.
10. Previous comment 10 not fully addressed. The handicap ramp on the north side of the roadway should be centered along lot line as to provide equal driveway access for the abutting lots.
11. Previous comment 11 not fully addressed. The plans must fully detail each type of ramp on plans.
12. Previous comment 12 "12. Detail each type of ramp to be used in project, include truncated domes." Plans must detail each type of ramp to be used for the subject project.
13. Previous comment 13 not fully addressed, see comment 8.
14. Previous comment 14 addressed.
15. Previous comment 15 addressed.
16. Previous comment 16 not fully addressed. Fully detail proposed scupper including scupper profile and section view.
17. Previous comment 17 not fully addressed. Provide a cross section extending along the proposed entrance including the adjacent scupper. Fully detail driveway.
18. Previous comment 18 not addressed. The "revised" drainage report only pertains to the detention basin sizing and does not include any scupper sizing? The report include the scupper calculations and approval from DSD.
19. Previous comment 19 not addressed. The "revised" drainage report only pertains to the detention basin sizing and does not include any roadway drainage analysis, please see the previous comment.
03/21/2006 THAUSER1 UTILITY CLEARANCES COT STREETS DIVISION Needs Review
03/21/2006 THAUSER1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Needs Review
03/21/2006 THAUSER1 UTILITY CLEARANCES PC WASTEWATER MGMT Needs Review
03/21/2006 THAUSER1 UTILITY CLEARANCES QUEST COMMUNICATION Needs Review
03/21/2006 THAUSER1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Needs Review
03/21/2006 THAUSER1 UTILITY CLEARANCES COX COMMUNICATION Needs Review
03/21/2006 THAUSER1 UTILITY CLEARANCES SOUTHWEST GAS CORP Needs Review
03/21/2006 THAUSER1 UTILITY CLEARANCES EL PASO NATURAL GAS Needs Review
03/21/2006 THAUSER1 UTILITY CLEARANCES KINDER MORGAN ENERGY Needs Review
03/22/2006 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approv-Cond We have reviewed these plans and have the following comments:

1. Sheet 3 - Handrail calls for standard detail 210 and it should be standard detail 105.

No further comments. 3/21/06
03/27/2006 DALE KELCH DOT TRAFFIC REVIEW Denied Traffic Engineering REJECTS this PIA submittal:

1. The no parking sign at lot 12 needs to be rotated 180 degrees.

2. Add an additional no parking sign at a midpoint in the cul-de-sac as was indicated on the 1st submittal redlines.

3. Add "Begin" and "End" placards as appropriate to the no parking signs as was indicated on the 1st submittal redlines.


D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
03/28/2006 TAMI HAUSER PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
03/28/2006 THAUSER1 CONSTRUCTION ESTIMATE REVIEW Needs Review
03/28/2006 TAMI HAUSER PIA COORDINATOR OUT TO CUSTOMER Completed