Permit Number: T06OT03228
Parcel: 11616302A

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T06OT03228
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2007 ELIZABETH EBERBACH ENGINEERING REVIEW Approved Floodplain use permit with elevation certificate required.
01/23/2007 ELIZABETH EBERBACH ENGINEERING REVIEW Approved January 23, 2007

FLOODPLAIN USE PERMIT # T06OT032228
PROJECT ADDRESS: 600 W St Marys Rd, Tucson Arizona 85701
APPLICANT'S NAME: Acacia Group (John Hucko, LA)
PROPERTY OWNER: City of Tucson Parks and Recreation

This parcel lies in a FEMA AO Zone (Depth 1) (map number 040076 C 2226K). The applicant is authorized to use a portion of the flood hazard area in the City of Tucson, Arizona, on the property described as:

Oury Park, 600 West St Marys Road, Tucson, AZ 85701, in a portion of OLD CITY FARM IRR PCL IN LOT 14 EXC FREEWAY, S 5.33 AC, Parcel 116-16-302A, in a portion of Township 14 South, Range 13 East, Section 11,

for the purpose of installation of Parks and Recreation equipment including electrical controller and pump.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and are particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit.

The following 11 conditions apply to this permit:
1) Within 5 (five) days of issuance of this permit, and through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "CONSTRUCTION PROCEEDING UNDER REQUIREMENTS OF CITY OF TUCSON FLOODPLAIN USE PERMIT # T06OT03228. FOR INFORMATION PLEASE CALL 791-5550."
2) This permit becomes invalid and is subject to additional floodplain review, if any required development permit changes the configuration of the improvement, or, if there is any further disturbance within the floodplain other than that outlined in this application. This floodplain use permit may be subject to conditions or restrictions designed to reduce or mitigate the potential damage or hazard to life or property resulting from development within the regulatory floodplain, floodway or erosion hazard areas as determined by the project engineer and accepted by the City of Tucson.
3) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.
4) All work shall conform to the approved Irrigation Plan sheet L-2 for the electrical controller and pump installation, sealed by John Hucko, LA (12-7-06), which is made part of this permit.
5) See the associated activity T06CM06292.
6) All service equipment, electrical and pump equipment shall be elevated at or above the regulatory flood elevation (2 feet above existing natural grade).
7) Certification of elevation must be prepared by a state registered land surveyor (RLS) and submitted to the Development Services Department Engineering Division, after the electrical controller and pump is installed, prior to final inspection for permit T06CM06292. A copy of the partially filled out elevation certificate is on file at DSD until the completed elevation certificate is returned.
8) Contractor will need to call for final inspection to permit T06CM06292 once elevation certificate has been completed by RLS for inspections by Development Services Department Engineering Division Inspection Team (791-5550) after the installation of the electrical controller and pump, and prior to final acceptance by DSD Inspector.
9) This Floodplain Use Permit and plans shall be kept in a readily accessible location on site at all times.
10) Any additional future disturbance of the floodplain shall have separate floodplain use permit applications submitted to this office for review and approval.
11) There shall be no stockpiling material, or storage of vehicles, other than that which is accepted by COT and as shown on the approved plans.

This Floodplain Use Permit will be automatically revoked and becomes invalid for non-compliance to conditions set forth in this permit. Also, this permit will expire one year from its date of issue. Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Development Services Department, Engineering Division.

(EXPIRATION DATE) Month: 2 Day: 25 Year: 2008

APPLICANT: John Hucko, LA (Acacia Group)
ADDRESS: 600 W St Marys Rd Tucson Arizona 85701
PHONE: (520) 407-9071
OWNER: City of Tucson, Parks and Recreation Department
ADDRESS: 900 S Randolph Wy, Tucson, Arizona 85716
PHONE: (520) 791-4873 (Contact Person: Kevin McElheny)


SIGNATURE OF APPLICANT DATE

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.
01/23/2007 ELIZABETH EBERBACH ENGINEERING REVIEW Approved DATE: January 23, 2007
TO: John Hucko, LA
SUBJECT: 600 West St Marys Rd, Oury Park improvements, T14S R13E Sec02, Ward 1
REVIEWER: Elizabeth Eberbach, PE, CPM, CFM
ACTIVITY: T06OT03228 (Floodplain Use Permit), T06CM06292

SUMMARY:
The subject property is entirely located within a Special Flood Hazard Area (SFHA), Zone AO (depth 1) as shown on the Flood Insurance Rate Map (FIRM), Community- Panel No. 04019C-2226K, effective date February 8, 1999.
Per Section 26-5.2 of the Tucson Code no development, storage of materials or equipment or other uses shall be permitted which acting alone or in combination with existing uses, create a danger or hazard to life or property. Any electrical equipment pump will need to be elevated 1 foot above the 100-year water surface elevation, and for this floodplain, the water surface elevation is 1 foot above existing grade. The plans indicate elevating the equipment 2 feet above existing grade, which is acceptable; Engineering Division of Development Services Department has received and reviewed the submittal package and recommends approval. Please be advised that since the subject property is located within the SFHA Zone AE floodplain, it will be required that an elevation certificate for the electrical panel / pump be filled out by an Arizona Registered Land Surveyor showing that the bottom of the equipment is above the regulatory flood elevation (one foot higher than the regulated water surface elevation of the base flood), and returned to our office. The following conditions apply to the floodplain use permit.

PERMIT CONDITIONS:
1) Within 5 (five) days of issuance of this permit, and through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "CONSTRUCTION PROCEEDING UNDER REQUIREMENTS OF CITY OF TUCSON FLOODPLAIN USE PERMIT # T06OT03228. FOR INFORMATION PLEASE CALL 791-5550."
2) This permit becomes invalid and is subject to additional floodplain review, if any required development permit changes the configuration of the improvement, or, if there is any further disturbance within the floodplain other than that outlined in this application. This floodplain use permit may be subject to conditions or restrictions designed to reduce or mitigate the potential damage or hazard to life or property resulting from development within the regulatory floodplain, floodway or erosion hazard areas as determined by the project engineer and accepted by the City of Tucson.
3) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.
4) All work shall conform to the approved Irrigation Plan sheet L-2 for the electrical controller and pump installation, sealed by John Hucko, LA (12-7-06), which is made part of this permit.
5) See the associated activity T06CM06292.
6) All service equipment, electrical and pump equipment shall be elevated at or above the regulatory flood elevation (2 feet above existing natural grade).
7) Certification of elevation must be prepared by a state registered land surveyor (RLS) and submitted to the Development Services Department Engineering Division, after the electrical controller and pump is installed, prior to final inspection for permit T06CM06292. A copy of the partially filled out elevation certificate is on file at DSD until the completed elevation certificate is returned.
8) Contractor will need to call for final inspection to permit T06CM06292 once elevation certificate has been completed by RLS for inspections by Development Services Department Engineering Division Inspection Team (791-5550) after the installation of the electrical controller and pump, and prior to final acceptance by DSD Inspector.
9) This Floodplain Use Permit and plans shall be kept in a readily accessible location on site at all times.
10) Any additional future disturbance of the floodplain shall have separate floodplain use permit applications submitted to this office for review and approval.
11) There shall be no stockpiling material, or storage of vehicles, other than that which is accepted by COT and as shown on the approved plans.

I can be reached at 791-5550, ext.2204 if you have questions.

Elizabeth Eberbach, PE, CPM, CFM
Civil Engineer
Engineering Division
Development Services Department