Permit Number: T06OT02675
Parcel: 11805020A

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T06OT02675
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2006 JASON GREEN ENGINEERING REVIEW Denied DATE: November 30, 2006
SUBJECT: 1202 S Camino Del Sierra- Culvert Installation
TO: Jeff Dana
LOCATION: T14S R13E Sec22, Ward 1
REVIEWERS: Jason Green, CFM
ACTIVITY: T06BU02479 (Grading Plan) and T06OT02675 (Floodplain Use Permit)


SUMMARY: Engineering Division of Development Services Department has received and reviewed the grading plan, Floodplain Use Permit and the submitted Drainage Statement, prepared by Stantec Consulting Inc., dated August 4, 2006, for the above referenced property. Engineering Division does not recommend approval of the grading plan, Floodplain Use Permit, or drainage statement at this time. Please provide the following for further review:

1. The HEC-RAS profile sheets can not be reviewed until the drainage statement provides all required hydrology information. The Watershed Map, Fig.2.1, and the associated hydrology calculations were not included in the submitted report.

2. Provide a revised drainage statement verifying the watershed map and hydrology calculation sheets for the associated drainage area for the unnamed wash. Label the topography, direction of flow, subject parcels and delineated watershed. Show on the watershed maps the entire delineated watershed used for the hydrologic and hydraulic calculations.

3. Provide verification for the 264 cfs discharge value used for the hydraulic calculations.

4. Revise the typographical error in the second paragraph of the introduction section to reference the proper FEMA FIRM Map Panel number.


GENERAL COMMENTS:

Please provide a revised drainage statement for review and approval that address the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

If you have any questions, or to schedule a meeting, I can be reached at 791-5550, extension 1189.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services