Review Status: Active

Review Details: FLOODPLAIN

Permit Number - T06OT01739
Review Name: FLOODPLAIN
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2006 JASON GREEN ENGINEERING REVIEW Denied DATE: July 7, 2006
SUBJECT: 5850 S Calle Rayo De Luna- Modification to Drainageway
TO: Casa Primera HOA Board of Directors
LOCATION: T15S R13E Sec12, Ward 1
REVIEWERS: Jason Green, CFM
ACTIVITY: T06OT01739 Floodplain Use Permit


SUMMARY: Engineering Division of Development Services Department has received and reviewed the Floodplain Use Permit for the above referenced property and does not recommend approval of the Floodplain Use Permit at this time. Please provide the following for further review:


1. DS Sec.10-02.2.3.1.2.D.1: Provide as an addendum to the submitted drainage report all relevant pages out of the previous referenced drainage report.

2. DS Sec.11-01.2.1: Provide a grading plan and grading plan application showing details of the proposed channel and all rock rip rap associated with slope and channel bottom stability.


GENERAL COMMENTS:

Please provide an addendum to the drainage report and a grading plan for review and approval that address the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

If you have any questions, I can be reached at 791-5550, extension 1189.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services