Permit Number: T06OT01427
Parcel: 106042070

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T06OT01427
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2006 SUZANNE BOHNET ENGINEERING REVIEW Denied The accepted value of the current structure, as provided by the detailed appraisal submitted by the applicant, is $172,195 (depreciated replacement cost of the church only - page 18 of the appraisal). This figure is accepted because for purposes of determining substantial improvement, market value pertains only to the structure in question. It does not pertain to the land, landscaping or detached accessory structures on the property.

The contractor's estimate is accepted, less the tax, at $127,223. The improvements divided by the market value is 74% and, therefore, this project is considered to be a substantial improvement. The addition to the existing structure is required to be elevated a minimum of one (1) foot above the water surface elevation of the 100-year flood.

In order to determine if the existing structure also needs to be brought into compliance with current floodplain management standards, please provide an estimate for the remodel only. Those figures may come from the submitted contractor's estimate. It is necessary to determine if the cost of the remodel improvements only divided by the market value of the Church exceeds 50%.

Therefore, in order to complete the processing of the FUP please provide an addendum to the contractor's estimate that includes only the cost of the remodel.

I would like to suggest a meeting to discuss further the FUP details and requirements. There are different scenarios with different processes that must be done in order to meet the requirements of the Floodplain Ordinance. Please contact me to set up a time at your convenience.