Permit Review Detail
Review Status: Completed
Review Details: FLOODPLAIN
Permit Number - T06OT01163
Review Name: FLOODPLAIN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/02/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | May 2, 2006 FLOODPLAIN USE PERMIT NO.: T06OT01163 RELATED PERMIT NO.: T06CM02311 ADDRESS: 300 E. 8th St. APPLICANT: Gilbert Electric The applicant is authorized to use a portion of the City of Tucson property described as (legal description): Tucson Lots 2 3 6 & Pt. N.36' Lot 7 Blk 74 1. This permit is for the purpose of temporary electric service installation within a mapped Special Flood Hazard Area (SFHA), Zone AE, as shown on the Flood Insurance Rate Map (FIRM), Community Panel No. 040076-04019C-2227K, effective date February 8, 1999. 2. The proposed development is impacted by the regulatory floodplain. For purposes of this permit, the following elevation requirements apply: Base Flood Elevation (BFE) = 2380.2 feet per the National Geodetic Vertical Datum (NGVD '29) Regulatory Flood Elevation (RFE) = 2381.2 feet per the National Geodetic Vertical Datum (NGVD '29) Service facilities, such as electrical equipment, shall be constructed at or above the RFE and either be placed on flood proof materials or be adequately flood proofed. 3. Any additional improvements, including block walls or fences, will require a separate Floodplain Use Permit prior to construction. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/16/2006 | VFLORES1 | OUT TO CUSTOMER | Completed |