Permit Number: T06OT00412
Parcel: 141090630

Address:
7600 S KOLB RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06OT00412
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2006 SUZANNE BOHNET ENGINEERING REVIEW Denied To: Scott Altherr, P.E., CFM, Castro Engineering
DATE: August 4, 2006
FROM: Suzanne Bohnet, CFM
Engineering Division

SUBJECT: 7600 S. Kolb Rd.
Grading for La Estancia de Tucson subdivision, Phase I, Lots 1-674
Floodplain Use Permit No. T06OT00412
Related Permit No.T05BU01019

RESUBMITTAL REQUIRED

The Floodplain Use Permit cannot be approved as submitted. Please include a response letter to the comments along with the corrected copies of the Grading Plan with your next submittal.

Floodplain Use Permit comments:
1. Please show on the Grading Plan the limits of the Special Flood Hazard Area (SFHA) floodplain as shown on FIRM Panel No. 04019C2855K.

Please note that until a Letter of Map Revision (LOMR) has been issued by FEMA all lots that lie within the mapped SFHA are required to have a Floodplain Use Permit and an Elevation Certificate. Additionally, flood insurance is mandatory for all federally backed mortgages or loans for any structures built in a SFHA until the LOMR is approved and made effective.

If you have any questions, I can be reached at 791-5550 x1188.
Suzanne Bohnet, CFM, Engineer Associate