Permit Number: T06EL02420
Parcel: 110103140

Address:
3144 N SWAN RD

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T06EL02420
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06EL02420 1/23/07

1. Demonstrate compliance with the current Tucson Lighting Code. Do not accept that the lighting is being modified less than 10% for this site. Please note that this does not apply to just the revision, but to the entire site, because the site lighting had not been inspected in the field.
2. Show fault calculations. Second request. Note that the AFC is depicted in the Grounding Electrode Conductor on the Riser Diagram.