Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide pole heights. For any pole over 20' in height, the detail and calculations for the pole and foundation shall be prepared and sealed by a Registered Structural Engineer.
2. It is unclear how the Aeris fixture would mount on a bollard.
3. Since the site area is 0.85 acre, the multiplier would be 0.85, not 2.6.
4. Put a note on the plans requiring the Special Inspection per Section 16 of the Tucson Lighting Code.