Permit Number: T06EL02234
Parcel: 12901045A

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T06EL02234
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06EL02234 11/14/06

1. Provide electrical drawings including site plan and line diagram.
2. Provide length of pole and depth of burial.
3. Provide attachment heights for conductor for both poles.
4. Provide TEP available fault current.
5. Have the Permit Clerk add a notice associating this permit for temporary power with the Activity Number of the permitted construction plans.